Operation
Selecting a Scene:
Typically, a 7-button station provides access to seven Presets (1-7). To select a Preset, press
and release the appropriate button on the keypad. The LED will change to its active state.
Programming
For programming instructions when using Vision.net Designer, please proceed to the
Vision.net software and its help files and/or manual.
TROUBLESHOOTING
In order to determine if a Vision.net network device is communicating, a network test signal
can be sent.
Network Test Signal
While in Standard Mode, a network test signal can be sent as follows:
Step 1. Press and hold Buttons [1], [3] and [6] for 3 or more seconds to enter Programming
Mode, when in Programming Mode, Button [1] will blink once every 2 seconds and
transmit a Set Station ID command on the SVN485 network.
Step 2. Verify that all other stations on the network are also blinking. If they are not, look
for a broken wire or a mis-wire between the previous blinking station.
Step 3. Exit Programming Mode by tapping Button [1] two more times.
Button Station Faceplate Alignment
When a button station is configured with less than a full complement of buttons, it is often
specified that they are center-aligned to the station instead of in numerical order. An alignment
image is available in the Vision.net Designer manual that - when printed and physically
aligned to the station - can help in identifying the alignment between physical buttons and
their configuration buttons. For example, a single button station will expose Button [4]. A 2-
button station will expose Buttons [3] and [5].
Refer to the Vision.net Designer manual for the alignment image.