Installation
6
55
Section 3
Installation
3.1 UV Disinfection System
The disinfection system is designed to be mounted either horizontally or vertically at the point-of-use or point-of-entry
depending on the specific flow rate of the unit.
Note: The ideal installation is vertical with the lamp connector on top. This is to prevent water damage from occurring on the
lamp pins and lamp connector.
•
The controller should be mounted either above or beside the chamber. Always mount controller horizontally to prevent
moisture from running down cordage and causing a potential fire hazard. Drip loops in all cordage connected to
controller is highly recommended. Refer to
.
•
The complete water system, including any pressure or hot water tanks, must be sterilized before start up by flushing with
chlorine (household bleach) to destroy any residual contamination. Refer to
•
The disinfection system is intended for indoor use only, do not install disinfection system where it may be exposed to the
weather.
•
Install the disinfection system on cold water line only, before any branched lines.
•
A 5 micron sediment filter must precede the disinfection system. Ideally, the disinfection system should be the last
treatment the water receives before it reaches the faucet.
Procedure:
1.
shows the installation of a typical disinfection system and the related components that may be used for the
installation. The use of a by-pass assembly is recommended in case the system requires “off-line” maintenance. In this
case, note the system requires a supplementary disinfection for the distribution system if any water is used during
by-pass condition. In addition, during by-pass, the water will NOT be disinfected and a “DO NOT CONSUME THE
WATER” tag should be physically installed on the by-pass assembly until such time as the system is sanitized and
returned to service. For more information, refer to
. If the water is to be consumed while the system is off-line,
the water must be boiled for twenty minutes prior to consumption.
C A U T I O N
Electronic controller must be connected to a Ground Fault Protected Circuit (GFCI) receptacle and the lamp connector ground wire connected to the
stainless steel chamber.
Figure 2
Figure 2 Disinfection System
Note:
UV system should
be the final piece of
treatment equipment
Optional flow restrictor
Note:
Mandatory for
NSF credited systems
Optional water
softener
To
drain
Optional by-pass
assembly
Optional by-pass
assembly
Optional
by-pass
assembly
Optional
solenoid
valve
Hot water pipes
Cold water pipes
Customer supplied
GFCI circuit to
match voltage
Water
meter
Main
water
shut-off
5 Micron
sediment
filter
Optional
carbon
filter
Optional
by-pass
assembly
Optional
drain
cock
Funcionamiento
5.2.3 Número total de días de funcionamiento
Para obtener esta lectura, pulse dos veces seguidas el botón de reinicio del temporizador y siga los pasos que se
, en relación al uso de esta función.
5.2.4 Fallo de lámpara (pantalla en blanco)
Consulte la
para ver una explicación de esta función.
Nota: En los sistemas VIQUA, el tono audible correspondiente al fallo de lámpara es una alarma continua, no la condición
intermitente (1 segundo encendida, 1 segundo apagada) de los sistemas VIQUA básicos.
5.2.5 Salida de solenoide
El controlador VIQUA, en combinación con el monitor de intensidad UV, proporciona un conector de salida de solenoide
IEC activado (voltaje de línea). (Nota: no es un contacto seco) Esta salida de solenoide está protegida por un fusible
aislado de 2 amperios sustituible. La conexión de esta salida al solenoide se puede realizar con el cable de alimentación
de solenoide IEC PN 260135. Cuando el monitor de intensidad UV detecta que el agua no se está tratando de la forma
adecuada e indica una intensidad de UV del 49 % o inferior, el relé interno se abre, impidiendo así que la alimentación de
CA llegue hasta la válvula de solenoide, normalmente cerrada. La válvula permanecerá cerrada (sin alimentación) hasta
que el nivel de UV suba por encima del 49 %, momento en el que el solenoide se abrirá, permitiendo así el paso del agua.
(Para activar temporalmente el funcionamiento de esta salida de solenoide hasta las 12 horas, consulte las instrucciones
de la
).
Nota: Durante la derivación, no consuma el agua hasta que el sistema haya vuelto a un estado seguro.
5.2.6 Salida de 4-20 mA (opcional)
Para poder transmitir los datos de intensidad UV a una ubicación remota mediante una señal de 4-20 mA, adquiera un
cable en "Y" (PN 260134) de su distribuidor. El cable en "Y" incluye 20 metros (65') de cable para la señal de 4-20 mA.
Figura 6 Instalación del solenoide
Válvula de
solenoide opcional
Содержание VH200
Страница 21: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 23: ...This page intentionally left blank ...