Chapter 3   Installation Guidelines

 

Manual VIPA HMI 

3-4 

 

HB160E - TP - RE_610-3B2I0 - Rev. 10/16 

In many cases, adherence to a set of very elementary rules is sufficient to 
ensure EMC. For this reason we wish to advise you to heed the following 
rules: 

 

During the installation of your automation units you should ensure 
that any inactive metal components are grounded via a proper large-
surface earth! 

 

• 

Interconnect any inactive metal components via low-impedance 
conductors with a large cross-sectional area. 

• 

Execute screw connections at coated and anodized metal parts either 
with special contact washer or remove the isolating protective film. 

• 

Install a central connection between the chassis ground and the 
earthing/protection system. 

 

Ensure that cabling is routed properly during installation! 

 

• 

Divide the cabling into different cable groups  
(High voltage lines, power supply lines, signal lines, data lines). 

• 

Always install high voltage lines and signal or data lines in separate 
channels or bundles. 

• 

Install signal and data lines as close as possible to any metallic ground 
surfaces (e.g. frames, metal rails, sheet metal). 

 

Ensure that the screening of lines is grounded properly! 

 

• 

Data lines must be screened. The screen has to be laid both-sided. 

• 

Analog lines must be screened. Where low-amplitude signals are 
transferred it may be advisable to connect the screen on one side of the 
cable only. 

• 

Attach the screening of cables to the ground rail by means of large-
surface connectors located as close as possible to the point of entry. 
Clamp cables mechanically by means of cable clamps. Route the 
connected screen to the modules without interruptions, but don't 
connect the screen again. 

• 

Ensure that the ground rail has a low-impedance connection to the 
cabinet/cubicle. 

• 

Use only metallic or metallic covers for the plugs of screened data lines. 

 

Basic rules for 
ensuring EMC 

Содержание HMI 610-3B2I0

Страница 1: ...VIPA HMI Touch Panel 610 3B2I0 Manual HB160E_TP RE_610 3B2I0 Rev 10 16 April 2010...

Страница 2: ...c Compatibility Directive 2006 95 EC Low Voltage Directive Conformity is indicated by the CE marking affixed to the product Conformity Information For more information regarding CE marking and Declara...

Страница 3: ...ssioning 2 4 Connection to a PLC system 2 12 Operating system Windows CE 2 13 Communication via ActiveSync 2 19 Integrated Server 2 22 Access to the network resources 2 29 Integration to WLAN network...

Страница 4: ...Contents Manual VIPA System HMI ii HB160E TP RE_610 3B2I0 Rev 10 16...

Страница 5: ...nd the dimensions that are required for the installation The chapter closes with the technical data Chapter 2 Deployment Touch Panel This chapter deals with the employment of the Touch Panel At the st...

Страница 6: ...for every chapter An index at the end of the manual The manual is available in printed form on paper in electronic form as PDF file Adobe Acrobat Reader Button Buttons are put in brackets e g NEXT or...

Страница 7: ...ve environments EX zone The manual must be available to all personnel in the project design department installation department commissioning operation The following conditions must be met before using...

Страница 8: ...Safety information Manual VIPA System HMI 4 HB160E TP RE_610 3B2I0 Rev 10 16...

Страница 9: ...l TP 610C from VIPA Besides of a description of the single components of the Touch Panel you will also find the dimensions that are required for the installation The chapter closes with the technical...

Страница 10: ...reby causing the module to become inoperable or unusable Modules that have been damaged by electrostatic discharges may fail after a temperature change mechanical shock or changes in the electrical lo...

Страница 11: ...trolling of process cycles Microsoft Windows CE V 5 0 full version as option Different HMI SCADA Runtime selectable 800MHz pulse frequency Work memory 128Mbyte about 1800Mbyte memory for user data on...

Страница 12: ...1 Slot for storage medium CF SD MMC 2 Connection for interfaces and power supply T o u c h P a n e l 1 2 3 3 Display with touch sensitive area touch screen 1 Compact Flash 2 MMC SD 1 2 Note Please reg...

Страница 13: ...422 485 interface COM 2 2 RS232 interface COM 1 3 MPI Profibus DP RS485 interface 4 2x Host USB A interface 5 Slave USB B interface 6 7 RJ45 jack for Ethernet Communication switch 8 Slot for DC 24V vo...

Страница 14: ...at My Device Slot for CF Here you may plug a CompactFlash type II The card may be plugged and removed during runtime and is immediately listed as Storage Card at My Device Every CompactFlash storage m...

Страница 15: ...8 TxD Line B 5 4 3 2 1 9 8 7 6 9 RxD Line B TxD A TxD B RxD A RxD B Shield RS422 Periphery 3 8 4 9 M5V TxD TxD RxD RxD P5V 5 6 Serial bus connection in 2 wire technology using half duplex mode Connec...

Страница 16: ...er rate up to 115 2kBaud Connection RS232 9pin plug Connection RS232 Pin RS232 1 CD 2 RxD 3 TxD 4 DTR 5 GND 6 DSR 7 RTS 8 CTS 1 2 3 4 5 6 7 8 9 9 RI RxD TxD GND TxD RxD 3 2 GND 5 RTS CTS 7 8 Shield RS...

Страница 17: ...nt is as follows Slave USB B Pin Assignment 1 VCC 2 DM 3 DP 2 1 3 4 4 GND The USB A interface of your PC can be connected to the Slave USB B interface of your Touch Panel deploying the USB programming...

Страница 18: ...tallation cutting W x H 287 x 217mm Front panel W x H 304 x 233mm Back side W x H x D 285 x 215 x 45mm Installation depth 45mm Note The degrees of protection are only guaranteed when the following is...

Страница 19: ...50 C Relative humidity max 85 Storing Transport temperature 20 to 60 C Display Size 10 4 211 2 x 158 4mm Resolution 600 x 800 800 x 600 Colors TFT color 64K colors MTBF Backlights 25 C ca 50000h Perip...

Страница 20: ...Chapter 1 Hardware description Manual VIPA HMI 1 12 HB160E TP RE_610 3B2I0 Rev 10 16...

Страница 21: ...onnection of the Touch Panel The main part of the chapter introduces Windows CE and the various communication options offered by the Touch Panel Topic Page Chapter 2 Deployment Touch Panel 2 1 Install...

Страница 22: ...le For the installation into a operating tableau and control cabinet fronts the Touch Panel requires the following front plate cutting W H Touch Panel W x H in mm 610 3B2I0 287 x 217 The fixing techni...

Страница 23: ...e flexible wires without end case as well as stiff wires You fix the conductors to the CageClamps like this DC 24V 1 2 3 1 Round opening for wires 2 Locking orange for screwdriver 3 Test point for 2mm...

Страница 24: ...bles are permitted Signal cables must not be let within the same cable shaft as high voltage cables As soon as the Touch Panel is provided by power supply the Touch Panel starts with user area of the...

Страница 25: ...of Permanent Registry With Backup the files of the flash disk and the Registry settings may be stored The backed up files may be restored by Restore With this button you may return to the user area W...

Страница 26: ...t Settings are activated With disabling Run on Startup the Touch Panel starts with the Windows operating system The functions preset at Settings are ignored With enabling Enable User Interface the Tou...

Страница 27: ...n the user respectively administrator area Here new buttons may be configured and assigned with corresponding programs You may choose Normal for the user area or Advanced for the administrator area Wi...

Страница 28: ...sword is defined you were prompted to enter the password If there is no password defined the administrator area is opened On delivery there is no password preset If you have forgot you password by ena...

Страница 29: ...re programs may be added which have to start in the background during startup e g VNC server or transport services With enabling the checkbox Autostart the program is always executed on startup after...

Страница 30: ...on the Touch Panel start via the button Control Panel the tool Com2 Configuration In the opened dialog window you activate the RS485 or the RS422 interface Default RS485 To remain the settings permane...

Страница 31: ...ot communicate via Movicon or zenon Via mode the interface could be set up on DP Slave Note It is possible to set up the DP slave with the tool via software but the hardware of the Touch Panel do not...

Страница 32: ...untime version of the HMI SCADA project engineering platforms your project is run able By using the according communication driver the Touch Panel supports connecting options to the PLC via MPI field...

Страница 33: ...ed to the absolute essentials with mouse operation touch screen that requires only small hardware resources Here the 2 icons My Device and Recycle Bin may exclusively be found at the Desktop The Profe...

Страница 34: ...selects the touched objects Characteristics with Windows CE Professional Plus V 5 0 In the Professional Plus version mouse functions are fully supported As soon as the touch screen is touched with th...

Страница 35: ...tings file browser etc 2 Open applications For every open application a button is to be found in the task bar There is no button for minimizing The switch between the applications happens via this but...

Страница 36: ...clusively entered via the software keyboard Keyboard Normal At pushed SHIFT key Meaning Home Position 1 End End BS Backspace up dn lt rt pgup Page pgdn Page ins Insert del Delete Tab Tabulator Shift C...

Страница 37: ...ou may use the grid pattern to preset a double click velocity and test this on the symbol below OK takes over the set value The calibration of the touch screens happens via the register Calibration by...

Страница 38: ...or the Touch Panel Baud Rate Enter here the transfer velocity of your MPI net The baud rate has to be identical for every MPI participant within the network According to the Baud Rate the network para...

Страница 39: ...Panel from the PC via ActiveSync you have to install it at the PC ActiveSync is freeware and may be downloaded from www microsoft de Download the ActiveSync from the Microsoft website and start the fi...

Страница 40: ...ouch Panel is recognized and the dialog window new partnership opens Choose yes that you want to fix a partnership and push Next In the now opening window de activate all synchronization settings and...

Страница 41: ...able the Touch Panel to be accessed via Ethernet you have to activate the option enable network connection in ActiveSync via File Connection Settings Disconnect the USB cable of the Touch Panel Confir...

Страница 42: ...via START Programs KuK Tools before switching off Per default the following server are integrated ftp server activated http server activated Telnet activated VNC not activated Phrases that are used in...

Страница 43: ...ns for an ftp connection If there are still problems with the ftp access ask your system administrator ftp access possible with version 5 5 or higher use passive ftp mode activate directory view for f...

Страница 44: ...nnect your Touch Panel with the network where your PC is a member via an Ethernet cable Switch on your Touch Panel As soon as your Touch Panel is connected via Ethernet you may monitor the IP address...

Страница 45: ...into the address bar IP address webadmin Enter the following into the authentification User name wince Password vipatp Remember to store your changes permanently in the registry via Start Programs KuK...

Страница 46: ...plication is not possible The establishing of a Telnet connection is password protected and has the following approach Start a Telnet client like for example MS DOS console at your PC and enter the fo...

Страница 47: ...Rev 10 16 2 27 After establishment of a Telnet connection the Touch Panel provides you with commands A list of possible commands with a short description is available via the command help By beginnin...

Страница 48: ...n the VNC server is on delivery deactivated The VNC connection establishment has the following approach Click on and open the Windows directory You have to deactivate every option at View Options to s...

Страница 49: ...test the physical connection a PING to the IP address of the network PC may be executed if there are problems while contacting the network PC The connection of a local name at the Touch Panel with a...

Страница 50: ...etwork printer For example you may print the content of the current directory with dir network printer The listing of all network connections of your Touch Panel happens via net use You may terminate...

Страница 51: ...s is opened Continue with WLAN integration Please regard only WLAN USB sticks are supported with the chip of the company Funkwerk inside PowerOFF the Touch Panel Plug the WLAN USB stick to the USB A i...

Страница 52: ...tivated For this open the register Wireless Information in the dialog window and click to the Advanced button The following window is shown By activating of Automatically connect to non preferred netw...

Страница 53: ...sed Switch off the power supply from your panel Plug the memory card to your panel and switch on the power supply again As soon as a new firmware is found at the memory card it is downloaded to the To...

Страница 54: ...Chapter 2 Deployment Touch Panel Manual VIPA HMI 2 34 HB160E TP RE_610 3B2I0 Rev 10 16...

Страница 55: ...Here we describe possible paths in which interference can enter the controller how you ensure the electromagnetic compatibility EMC and how to approach shielding and screening issues Topic Page Chapte...

Страница 56: ...industrial environments and complies with EMC requirements to a large degree In spite of this you should implement an EMC strategy before installing any components which should include any possible s...

Страница 57: ...te to the time wise change of the voltage Interference through parallel signal lines Static discharge of the personnel Contactors Inductive coupling Automation System Disruptor inductive coupling line...

Страница 58: ...groups High voltage lines power supply lines signal lines data lines Always install high voltage lines and signal or data lines in separate channels or bundles Install signal and data lines as close...

Страница 59: ...cent lamps Create a single reference potential and ensure that all electrical equipment is grounded wherever possible Ensure that grounding measures are implemented effectively The controllers are ear...

Страница 60: ...may only get voltage in case of an error The ground must not adopt dangerous contact voltage even in case of an error Thus you have to connect the ground with the protected earth conductor To avoid gr...

Страница 61: ...to divide the cables in different groups and install each group itself Group A screened bus and data lines screened analog lines unshielded lines for direct voltage 60V unshielded lines for alternatin...

Страница 62: ...be installed on metallic cable trays A galvanic connection must be provided for joints between cable trays You must abide by the applicable lightning protection and grounding regulations when install...

Страница 63: ...mm 2 Cu for equipotential bonding conductors up to 200m 25mm2 Cu for equipotential bonding conductors exceeding 200m Use copper or galvanized steel for equipotential bonding conductors These must be c...

Страница 64: ...recommended that the remove the insulation from the screened cable without cutting the screen and to attach this point to the screening neutral rail Note Potential differences can give rise to an equ...

Страница 65: ...ections of DC activated inductors Connections of AC activated inductors using a diode using a Z diode using a varistor using RC network Every cubicle must be provided with a power outlet for the PU Th...

Страница 66: ...l contact washer Have the connection been protected from corrosion e g by means of grease Have doors been grounded by means of grounding straps connected to the body of the cubicle Cable routing Cabli...

Страница 67: ...Flash disc 1 6 ftp server 2 23 H http server 2 25 I Installation 2 2 cutting 2 2 guidelines 3 1 L Login data 2 22 M Memory management 1 6 MMC 1 6 MPI interface 1 7 MPI parameters 2 18 N net use 2 29...

Страница 68: ...Index Manual VIPA System HMI A 2 HB160E TP RE_610 3B2I0 Rev 10 16 M Stich...

Отзывы: