Chapter 3 Deployment CPU 21x-1Bx06
Manual VIPA System 200V
3-12
HB97E - CPU - RE_21x-1Bx06 - Rev. 13/20
Enter the number of retentive memory bytes from memory byte 0 onwards.
Retentive values > 1024 are not allowed.
Enter the number of retentive
S7 timers
from T0 onwards. Each
S7 timer
occupies 2bytes.
Enter the number of retentive
S7 counter
from C0 onwards.
These parameters are not relevant.
Here the priorities are displayed, according to which the hardware interrupt
OBs are processed (hardware interrupt, time-delay interrupt, async. error
interrupts).
Here the priorities may be specified according to which the time-of-day
interrupt is processed.
With priority "0" the corresponding OB is deactivated.
Activate the check box of the time-of-day interrupt OBs if these are to be
automatically started on complete restart.
Select how often the interrupts are to be triggered. Intervals ranging from
every minute to yearly are available. The intervals apply to the settings
made for
start date
and
time
.
Enter date and time of the first execution of the time-of-day interrupt.
This parameter is not supported.
Here the priorities may be specified according to which the corresponding
cyclic interrupt is processed. With priority "0" the corresponding interrupt is
deactivated.
Retentive Memory
Number of Memory
Bytes from MB0
Number of S7
Timers from T0
Number of S7
Counters from C0
Areas
Interrupts
Priority
Time-of-day
interrupts
Priority
Active
Execution
Start date / time
Process image
partition
Cyclic interrupts
Priority
Содержание CPU 214
Страница 1: ...VIPA System 200V CPU Manual HB97E_CPU RE_21x 1Bx06 Rev 13 20 May 2013...
Страница 4: ...Contents Manual VIPA System 200V ii HB97E CPU RE_21x 1Bx06 Rev 13 20...
Страница 8: ...Safety information Manual VIPA System 200V 4 HB97E CPU RE_21x 1Bx03 Rev 13 20...
Страница 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E CPU RE_21x 1Bx06 Rev 13 20...