The electronic controller allows the customer to select a temperature form 45
°
F
to 75
°
F. When the thermistor senses a temperature above the setting value, the
electronic controller will turn on the compressor and fan motors. Once the
selected temperature is sensed, the electronic will turn off the cooling unit.
A. Resistance
1. Unplug WINEMATE cooling unit or disconnect power.
2. Disconnect the connector with the red and white wires connected to the
input of the electronic controller.
3. Touch and hold one ohmmeter probe to one terminal on the electronic
controller, then touch and hold the other probe to the other terminal.
4. The ohmmeter should show a reading of 825
Ω
±
10%.
5. Reconnect the wire connector to the electronic controller.
B. Input Live Voltage
Figure 3-3
- 16 -