background image

                                                       

 

                       

 

15 

Installer’s Instructions 

 

Federal law requires that WINE-MATE split cooling systems be 

installed by an EPA certified refrigeration technician

 

1.  General Instructions 

 
WINE-MATE  split  system  is  shipped  as  components  and  is  ready  for  use  only 
after a certified refrigeration technician has properly installed the system. Proper 
installation is critical. Vinotemp can only warrant the quality of the components. 
The  installation  and  proper  operation  of  the  system  must  be  warranted  by  the 
installer. Installation of the system must be done in accordance with all state and 
local building and electrical codes.  
The  condensing  unit  and  evaporator  unit  are  connected  by  a  liquid  line  and  an 
insulated  suction  line  that  are  supplied  by  the  installer.  These  lines  must  be 
properly  sized  for  the  distance  between  the  two  units.  After  the  units  and  lines 
are  connected,  the  system  must  be  checked  for  restriction,  pressurization  and 
leak.  Then  the  system  must  be  evacuate  and  charged  with  refrigerant. 
Refrigerant amount will vary depending on the length of line set. 
 

Parts included: 
 

Evaporator Unit (liquid line solenoid valve and expansion valve installed) 
Condensing Unit (discharge and suction valves installed) 
Liquid Filter 
Liquid Indicator 
Temperature Controller (4.5”LX4.5”WX3.75”D) + Air Probe 
 

Parts not included: 
 

Liquid line copper tubing 
Suction line copper tubing 
Insulated ducts 
 

Содержание WINE-MATE WM-2520SSH

Страница 1: ...www winemate com www winemate com Duct Split Cooling System Installation Operation Care Manual WM 2520SSH WM 4520SSH WM 6520SSH WM 8520SSH www vinotemp com www vinotemp com...

Страница 2: ...d and save these instructions these instructions Important Safety Information WARNING Do not use a ground fault interrupter GFI A dedicated 10 AMP circuit for WM 2520 4520SSH and 15 AMP for WM 6520 85...

Страница 3: ...le of Contents Cellar Construction 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 15 Electrical Wirings 26 Customer Support 30 Warran...

Страница 4: ...rature surrounding the enclosure shall not exceed the temperature of the cellar by more than 25 F No cellar wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer t...

Страница 5: ...d away from the evaporator unit 50 ft so that noise and compressor vibration are isolated SSH evaporator units are designed to provide chilled air to wine a cellar through ducts and can be located up...

Страница 6: ...2520SSH WM 252SFCH 22 5x15 875 x14 375 11 WM 252SCU 18x14x12 2100 180 230 R134a 220V 50Hz 0 5A 220V 50Hz 3A 35 40 WM 4520SSH WM 452SFCH 25 125x22 875 x16 375 18 WM 452SCU 18x14x12 3700 320 900 R134a 2...

Страница 7: ...lock unlock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock th...

Страница 8: ...e temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of bottles temperature setting and surrou...

Страница 9: ...be faulty min 30 CF temperature unit F C F Fahrenheit rES display resolution in integer dLy temperature display delay min 1 ot probe calibration 0 LS minimum set point 50 US maximum set point 65 idF d...

Страница 10: ...te hygrometer to monitor the humidity 10 How to set alarm call 1 Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the set point Set 2 In order to t...

Страница 11: ...lean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Removing...

Страница 12: ...mperature is mainly controlled by the average air temperature If the set point is 55 F with the differential 4F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it is...

Страница 13: ...ide and leave minimum 1 foot clearance for the ambient air intake side c Check for excessive size d Check for installation location e Clean condenser f Check for fan and air short circulation 8 Conden...

Страница 14: ...flow restriction d Drain restricted or unit not level and water overflowing e Drip tray leak No water overflow but leak a Check for air leak b Use drain line c Check supply air flow or air TD d Clean...

Страница 15: ...14 high ambient temperatures or airflow restriction d Defective components d Call service for checking internal loose inadequate lubrication and incorrect wirings...

Страница 16: ...and electrical codes The condensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer These lines must be properly sized for the...

Страница 17: ...16 CAUTION Liquid and suction line locations may differ from what are shown here please check on the units for proper installation Fig 3 WM 252 852SFCH Evaporator Unit...

Страница 18: ...17 Fig 4 WM 252 452SCU Condensing Unit Fig 5 WM 652 852SCU Condensing Unit...

Страница 19: ...ditional wires are needed 18 gauge wires may be used to extend the air probe 4 If the air probe is installed in a return duct the evaporator fans shall be running all the time Meanwhile due to the tem...

Страница 20: ...ng unit will build up and the cooling system will not operate properly 2 Condensing unit shall be elevated to avoid possible flooding and shaded from direct sun It shall not be exposed to temperatures...

Страница 21: ...e control if applicable for pump down Suction pressure setting Cut out 5 psig Cut in 25 psig Differential 20 psig Head pressure setting Cut out 230 psig Cut in 150 psig Differential 80 psig It may nee...

Страница 22: ...Head pressure setting Cut in 170 psig Cut out 110 psig Differential 60 psig It closes on rise of pressure It may need to adjust the setting in the field to avoid fan short cycle Fig 13 Condenser Fan...

Страница 23: ...0 ft or the line set exceeds 75 ft use both inverted U trap and suction accumulator 3 If the condensing unit is located more than 10 ft above the evaporator unit use U trap to aid oil returning to the...

Страница 24: ...nob to the lowest speed position then rotate the setting located on the side or front clockwise to decrease the minimum speed or counter clockwise to increase the minimum speed The minimum speed shoul...

Страница 25: ...pressure Low superheat and high subcooling 4 High to normal suction pressure and high head pressure Low subcooling 5 High suction pressure and high head pressure Low superheat and low subcooling 6 Hi...

Страница 26: ...2 Expansion valve restricted 13 Both evaporator and condenser restricted liquid and suction lines connected wrong 14 Liquid line restricted before receiver 15 Condenser restricted 11 Condensing Unit T...

Страница 27: ...are the field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the co...

Страница 28: ...27 Fig 17 WM 6520SSH Electrical Wiring Diagram Fig 18 WM 8520SSH Electrical Wiring Diagram...

Страница 29: ...28 Fig 19 Low Ambient Temperature WM 2520 4520SSH LA Electrical Wiring Diagram Fig 20 Low Ambient Temperature WM 6520SSH LA Electrical Wiring Diagram...

Страница 30: ...29 Fig 21 Low Ambient Temperature WM 8520SSH LA Electrical Wiring Diagram...

Страница 31: ...0 Customer Support If you need further assistance please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp co...

Страница 32: ...and is in lieu of all other warranties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any...

Страница 33: ...NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its units to properly...

Отзывы: