background image

                                                       

 

                       

 

- 12 -

high or not 
cooling and 
running 
continually   

b.  Cellar too large 
c.  Ambient temperature too high 
d.  Exhaust restricted  
 
 
 
e. Malfunctioning 

fans 

 
f. 

Evaporator or condenser airflow 

 

g. Dirty 

Condenser 

h. Iced 

evaporator 

i. Refrigeration 

system 

restriction 

j. Refrigerant 

leak 

k.  Undercharge or overcharge 
l. Failed 

components 

 

b.  Check for excessive size   
c.  Check installation location 
d.  Leave minimum 3 feet clearance for 

the hot air exhaust side and leave 
minimum 1 foot clearance for the 
ambient air intake side  

e. Check for both evaporator and 

condenser fans  

f.  Check for air restrictions, air short-

circulation, grille directions 

g. Clean 

condenser 

h.  Defrost and reset temperature 
i. Call 

service 

j. 

Call service  

k.  Call service  
l.  Check compressor windings, start 

relay and overload protector 

7. Unit running 

too long 

 

a.  Improper cellar insulation & seal 
 
b. Exhaust restricted 
 
 
 
c.  Cellar too large 
d. Ambient temperature higher > 

90

°

e. Dirty Condenser 
f.  Improper condenser air flow 
 

a. Check insulation, gasket and door 

opening 

b.  Leave minimum 3 feet clearance for 

the hot air exhaust side and leave 
minimum 1 foot clearance for the 
ambient air intake side 

c.  Check for excessive size   
d.  Check for installation location 

 

e. Clean condenser 
f. Check for fan and air short 

circulation 

8. Condenser 

fan running 
but 
compressor 
not running

 

a.  Incorrect or loose wirings 
b. Failed 

components 

 

c. 

Liquid refrigerant in the 
compressor 

a.  Check all wirings and  connections 
b.  Check start relay, start capacitor, 

overload protector, compressor. 

c. Call 

service. 

9. Compressor 

running but 
condenser 
fan not 
running

 

a.  Fan blade stuck 
b.  Incorrect or loose wirings 
c. Failed 

motors 

d.  Fan cycle control 

a.  Check for proper clearance 
b.  Check all wirings 
c. Call 

service 

d.  Check for setting 

10.Temperature  

high, 
compressor 
stopping 
and starting 
but very 
short 
running time

 

a. Failed 

components 

 
b. Improper 

condenser 

airflow 

c. Dirty 

condenser 

d.  Overcharge of refrigerant 
e.  Discharge or suction pressure 

too high 

a.  Check compressor windings, start 

relay and overload protector. 

b.  Check for condenser fan  
c. Clean 

condenser 

d.  Call service for removing refrigerant 
e.  Call service for information 
 

11.Evaporator 

fan running 
too long 

a. 

Post-compressor fan running 
mode for humidity modulation 

 

a. Reset FON 
 

12. Evaporator 

a.  Incorrect or loose wirings 

a.  Check all wirings and  connections 

Содержание WINE-MATE WM-1500SSW

Страница 1: ...te e c co om m Wall Split Cooling System Installation Operation Care Manual WM 1500SSW WM 2500SSW w ww ww w v vi in no ot te em mp p c co om m R Re ea ad d a an nd d s sa av ve e t th he es se e i in ns st tr ru uc ct ti io on ns s ...

Страница 2: ... 1 Important Safety Information WARNING Do not use a ground fault interrupter GFI A dedicated 20 AMP circuit is required ...

Страница 3: ...ble of Contents Cellar Construction 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 23 Customer Support 25 Warranty 26 ...

Страница 4: ...perature surrounding the enclosure shall not exceed the temperature of the cellar by more than 25 F No cellar wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer to insure lights are not left on when the cellar is not occupied The cooling system will not be able to maintain the proper temperature if fresh moisture laden air is constantly being introduced to t...

Страница 5: ...ng units can be located away from the wine cellars 50 ft so that noise and compressor vibration are isolated SSW evaporator units can be installed inside a wine rack or between two wall studs making them an idea choice for wine cabinets or small wine rooms Fig 1 SSW Wall Split Cooling System NOTE Capacity is determined under the cellar the cellar ambient and the condensing unit ambient temperature...

Страница 6: ...it L xD xH Cond Unit L xD xH Btu h CFM Cellar Size cu ft Refrigerant Electrical Evap Unit Cond Unit Weight lb Evap Unit Cond Unit WM 1500SSW WM 15SFCW 16x5 5x36 WM 150SCU 18x14x12 1500 105 150 R134a 115V 60HZ 0 35A 115V 60HZ 3 1A 25 30 WM 2500SSW WM 25SFCW 16x5 5x36 WM 250SCU 18x14x12 2500 175 250 R134a 115V 60HZ 0 71A 115V 60HZ 5 7A 30 40 Also see Fig 3 4 for further info ...

Страница 7: ...To lock unlock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys press up down keys until PON is displayed 3 Display During normal operating conditions the display shows the value measured by the air regulation probe In case of active alarm the temperature...

Страница 8: ...Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of bottles temperature setting and surrounding temperature Allow 24 hours to stabilize the temperature for each new temperature setting operation 3 How to see temperature set point 1 Press and immediately release the SET key th...

Страница 9: ...ALL lower than the set point Set 2 In order to test the call function set parameters Ald 0 and dAO 0 After testing set Ald 60 and dAO 23 9 How to set low cellar temperature heater The heater turns on at set point SAA minus regulation differential Shy the heater turns off at heater set point SAA NOTES Use a forced air heater to warm up the wine cellar If there is a thermostat on the heater bypass i...

Страница 10: ...US maximum set point 65 LS minimum set point 50 idF defrost cycle interval time hour 12 MdF defrost cycle endurance time min 30 ALC temperature alarm type rE relative to set point ALU high temperature alarm 10 ALL low temperature alarm 10 AFH alarm recovery differential 5 ALd temperature alarm delay min 60 dAO temperature alarm delay on startup hr 23 SAA heater set point 40 SHy heater regulation d...

Страница 11: ...Clean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Removing Remove the excessive condensate if it is accumulated in the wine cellar at high humidity conditions ...

Страница 12: ... temperature is mainly controlled by the average air temperature If the set point is 55 F with the differential 4F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost cycle and turns off at 55 F of air temperature The average air temperature is 57 F and then the wine temperature is around 57 0 5 F The air is light enough to change...

Страница 13: ...ust side and leave minimum 1 foot clearance for the ambient air intake side c Check for excessive size d Check for installation location e Clean condenser f Check for fan and air short circulation 8 Condenser fan running but compressor not running a Incorrect or loose wirings b Failed components c Liquid refrigerant in the compressor a Check all wirings and connections b Check start relay start ca...

Страница 14: ... leak No water overflow but water leak a Check for any air leak b Use drain line c Check supply air flow or air TD crossing evaporator d Clean the drip tray e Seal the leak using silicone sealant 15 Condensate inside ducts a Drain line restricted b Continually running not stopping c Too cold supply air a Check for drain b raise temperature setting or increase defrost cycle c Increase air flow or r...

Страница 15: ...state and local building and electrical codes The condensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer These lines must be properly sized for the distance between the two units After the units and lines are connected the system must be checked for restriction pressurization and leak Then the system must be evacuate and ...

Страница 16: ... 15 CAUTION Liquid and suction line locations may differ from what are shown here please check on the units for proper installation Fig 3 WM 15 25SFCW Evaporator Unit ...

Страница 17: ...rect blow installation leave 2 clearance for a deflector installation air return shall be unobstructed minimum 6 3 A grille can be used to cover the supply and return with 0 2 clearance or 2 3 ft long duct can be added 4 There is a gravity drain system used so the unit shall be installed level or with a slight slope downward the drain connection and the drain line shall be installed slope down tow...

Страница 18: ...shall be elevated to avoid possible flooding and shaded from direct sun It shall not be exposed to temperatures higher than 110 F or lower than 50 F 3 Leave minimum 5 ft clearance for the exhaust side and leave minimum 1 foot clearance for the ambient air intake side 4 Service valve operations 1 Process Manometer 2 Receiver Discharge or Compressor Suction 3 Liquid Line or Suction Line 4 Pressure C...

Страница 19: ...e pulled out of the temperature controller around 5 ft if additional wires are needed 18 gauge wires may be used to extend the air probe 5 Checking Control Settings 1 Use of the encapsulated pressure control if applicable Fixed suction pressure setting Cut in 32 psig Cut out 10 psig Fig 9 Fixed Pressure Control 2 Low ambient condition kit if applicable A Use of the crankcase heater The crankcase h...

Страница 20: ... liquid line in the evaporator unit 1 The installation order starts from condensing unit including receiver and discharge valve liquid line filter drier moisture liquid indicator liquid line to evaporator unit including liquid line connection solenoid valve expansion valve and suction line connection returning to insulated suction line suction valve and then back to condensing unit 2 If the conden...

Страница 21: ...he condensing unit Only turn on the compressor after the condensing unit has been powered for 12 hours 1 Evacuate the system both discharge and suction valves must be in the middle positions during evacuating 2 Charge the system through both suction and discharge valves with refrigerant using the suggested amount both discharge and suction valves must be in the middle positions during charging 3 C...

Страница 22: ...verify if the superheat at the evaporator unit is around 9 18 F at 55 F wine cellar temperature under high low ambient temperatures 7 If the superheat is high check the subcooling first to know if the refrigerant charge is sufficient If the charge is not sufficient add more refrigerant If the charge is good then increase the evaporator suction pressure by turning the hex nut 5 16 clockwise Liquid ...

Страница 23: ...ure High superheat and normal subcooling 13 Low suction pressure and high head pressure High superheat and high subcooling 14 Low suction pressure and high head pressure High superheat and high subcooling 15 low to normal suction pressure and high head pressure Normal to high superheat and high subcooling 1 Compressor may be bad 2 Expansion valve opened too much oil 3 Overcharge 4 Non condensable ...

Страница 24: ... are the field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the condensing unit Fig 13 WM 1500 2500SSW Wiring Diagram ...

Страница 25: ... 24 Fig 14 Low Ambient Temperature WM 1500 2500SSW LA Electrical Wiring Diagram ...

Страница 26: ...25 Customer Support If you need further assistance please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp com ...

Страница 27: ...nties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products shall void this warranty Service under Warranty This service is provided to customers within the continental UNITED STATES only VINOTEMP cooling units are warranted to produce the stated number of BT...

Страница 28: ...F USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its unit...

Отзывы: