B. Dual Control 

 

Fig. 4 Dual Adjustable Pressure Control 

 

8. 

Use of the encapsulated pressure control (if applicable)

 

 

Fixed suction pressure setting: Cut in = 32 psig; Cut out = 10 psig 

 

 
9. 

Use of the condenser fan control (if applicable for low ambient kit)

 

 

Head pressure setting: Cut in=170 psig; Cut out=120 psig; Differential=50 psig 

 

It may need to adjust the setting in the field to prevent short fan cycle. 

 

10. 

Use of the crankcase heater (if applicable for low ambient kit)

 

 

The crankcase heater is installed around the lower part of the compressor and 
shall be turned on all the time.  The heater is self-regulated. 

 

CAUTION:  
TURN OFF THE COMPRESSOR SWITCH BEFORE POWER THE 
CONDENSING UNIT.  ONLY TURN ON THE COMPRESSOR AFTER THE 
UNIT HAS BEEN POWERED FOR 24 HOURS. 

 

Содержание WINE-MATE 250SCU

Страница 1: ...a liquid line and an insulated suction line that are supplied by the installer These lines must be properly sized for the distance between the two units After the units and the lines are installed th...

Страница 2: ...ion 1 Process Manometer 2 Receiver Compressor Suction 3 Liquid Suction Line 4 Pressure Control Back Position Process and manometer port closed for normal operation Front Position Connection to liquid...

Страница 3: ...evaporator unit including liquid line connection solenoid valve expansion valve and suction line connection returning to insulated suction line suction valve and then condensing unit Use inverted siph...

Страница 4: ...CONNECTION SIZES OF CONDENSING UNIT AND THE LINE CONNECTION SIZES OF EVAPORATOR UNIT ARE NOT NECESSARY THE SAME AS THE ABOVE SPECIFIED LINE SIZES IF THE CONDENSING UNIT IS INSTALLED ABOVE THE EVAPORAT...

Страница 5: ...pressure High superheat and high subcooling o low to normal suction pressure and high head pressure High to normal superheat and high subcooling g Undercharge h Liquid line restricted after receiver...

Страница 6: ...n 170 psig Cut out 120 psig Differential 50 psig It may need to adjust the setting in the field to prevent short fan cycle 10 Use of the crankcase heater if applicable for low ambient kit The crankcas...

Страница 7: ...led components d Liquid refrigerant in the compressor e Low pressure switch shutting down the system a Check for proper voltage b Check all wirings and connections c Check start relay start capacitor...

Отзывы: