02973 - Connected dial thermostat
SMART HOME VIEW WIRELESS
Download the View Wireless
App from the stores onto the tablet/smartphone
you will be using for configuration.
You will need:
Gateway art. 20597-19597-16497-14597
View App
for management via smartphone/tablet
Alexa, Google Assistant, Siri and Homekit voice assistants for possible voice operation
CONFIGURATION IN
1.
Create your Installer account on MyVimar (on-line).
2.
Wire all the devices in the system (2-way switches, relays, thermostats, gateway, etc.).
3.
Start the View Wireless App and log in with the credentials you just created.
4.
Create the system and the environments.
5.
Associate all the devices with the environments, except for the gateway (which should be
associated last).
To associate the thermostat:
• Select “Add” (
), choose the environment to place it and give it a name
• Select
; activate the Bluetooth connection on your tablet/smartphone and approach
the thermostat
• Press
for 5 s; the ring flashes blue and association is complete.
6.
For every device, set the function, the parameters and any accessory devices (wired or radio
control and related function).
7.
Transfer the configuration of the devices to the gateway and connect it to the Wi-Fi network.
8.
Transfer the system to the Administrator user (who must have created his/her profile on
MyVimar).
For full details, see the View Wireless App manual that can be downloaded from the www.
vimar.com website.
RESETTING THE THERMOSTAT
The reset restores the factory settings. Within the first 5 minutes of powering, press
for 30
s; during these 30 s the ring flashes blue and then emits 2 white flashes to confirm the operation.
INSTALLATION RULES.
• Installation and configuration must be carried out by qualified persons in compliance with the
current regulations regarding the installation of electrical equipment in the country where the
products are installed.
• The C-NO contact of the relay must be protected against overloads by installing a device, fuse
or automatic 1-way switch, with a rated current not exceeding 10 A.
• Do not connect a SELV circuit to the C-NO terminals as there is no double insulation on the
L-N terminals
• The device must be installed in a flush mounting box or surface mounting box with the related
mounting frames and cover plates, at a height of 1.5 m above floor level, in a suitable position
for the correct detection of the room temperature, avoiding installation in recesses, behind
doors and curtains, areas affected by heat sources or subject to the flow of forced heating/
cooling ventilation sources or affected by atmospheric factors. Avoid in particular installation
on perimeter walls or in association with devices which generate heat (e.g. dimmers or lamps).
CHARACTERISTICS.
• Rated supply voltage: 100-240 V~, 50/60 Hz.
• Dissipated power: 0.55 W.
• RF transmission power: < 100mW (20dBm).
• Frequency range: 2400-2483.5 MHz.
• Terminals:
- 2 terminals (L and N) for line and neutral
- 2 terminals for external temperature probe (art. 02965.1 and 20432-19432-14432)
Maximum length of the external sensor connection cable: 10 m.
Use a twisted cable with a minimum cross-section of 0.5 mm
2
(art. 01840).
- 2 C-NO relay terminals.
• Relay output with voltage-free contact: 5(2) A 240 V~
• Current settable setpoint: 4°C - 40°C.
• Temp. measurement precision (integrated probe): 0.5°C b15°C and 30°C, 0.8°C at
the extremes
• For use for Heating/Air Conditioning (winter/summer).
• Operating modes: Automatic, Manual, Reduction, Absence, Protection, Off, Timed Manual
• Temperature control algorithms: ON/OFF or configurable PID
• 4 front buttons for control and configuration/reset
• RGB LED for configuration status (flashing blue) and output status (configurable colour) signalling
• Operating temperature: T40 (0 °C +40 °C) (indoor use)
• Protection degree: IP30
• ErP classification (EU Reg. 811/2013): - ON/OFF: class I, contribution 1%. - PID: class IV,
contribution 2%.
1
• Short press = degrees Celsius/Fahrenheit selection
• Long press (5 s) = the thermostat enters the configuration phase (bt)
• Prolonged press (30 s) within the first 5 min of powering = device reset (rst)
Display brightness and RGB LED in standby setting
• 1st press = current brightness display
• Subsequent presses = cyclic display of available brightness values L-3 (high), L-2
(medium), L-1 (low) and L-0 (off).
A
Display
• bt = devices in Bluetooth configuration
• off = thermostat off; on = thermostat on
• °C = degrees Celsius; °F = degrees Fahrenheit
• L-0, L-1, L-2, L-3 = brightness in standby (from the lowest to the highest)
• H = heating; C = air conditioning
• opn = open window (associated with the thermostat via magnetic contact art.
03980)
B
Dial
C
Lightable ring
• Power on and off.
Upon power on or off, the thermostat starts in the last operating mode associated
with it set via the View App.
• Heating or air conditioning mode selection.
Ring signalling
All flashing blue = thermostat in configuration mode
All lit amber* = thermostat in heating mode and relay active
All lit blue** = thermostat in air conditioning mode and relay active
1
• Lit amber * = thermostat in heating mode and relay not active
• Lit blue ** = thermostat air conditioning mode and relay not active
In standby, the brightness is set during configuration; otherwise, the value is the
maximum one.
2
• Flashing red = the thermostat, in automatic mode, has lost the hourly value and
has therefore switched to manual mode.
When it receives the hourly value from the gateway again, the thermostat returns
to automatic mode and the flashing ends.
* Amber with automatic colour or of the selected colour.
** Blue with automatic colour or of the selected colour.
A
B
C
2
• Device in class II
• Number of manual cycles: 3,000
• Number of automatic cycles: 100,000
• Type of contact opening: micro-disconnection
• Type of action: 1BU
• Tracking index: PTI175
• State of pollution: 2
• Rated pulse voltage: 4000 V
• Software class: A