By-alarm additional power supply unit 50/60 Hz 1.5 A, metal enclosure 

with battery compartment, surface mounting.

TECHNICAL CHARACTERISTICS

• Power supply for 

art. 01717

230 V~

 (+10% / -15%) 50 Hz

• Power supply for 

art. 01717.120

120 V~

 (+10% / -10%) 60 Hz

• Stabilized voltage: 13.8 Vdc nominal (± 2%)
• Rated current: 1.5 A total
• Ripple at 230 V~ -15%: 10 mV at maximum load
• Ripple at 120 V~ -10%: 350 mV at maximum load
• Autotest: dynamic and programmable
• Operating temperature: -10..+40 °C (indoor use)
• Dimensions: 345x435x125 mm
• Degree of safety 2 (EN 50131-6)
• Ambient class II (EN 50131-6)

BATTERIES

Sealed 12 V lead batteries must be used with flammability class UL94-HB; the cables 
for connecting the battery are designed for Faston connectors. 
For the screw connection, the Faston connector is to be cut and eyelet terminals 
must be fixed to the ends of the cables.

CAUTION: Danger of explosion if the battery is replaced with one of the wrong 
type.

OPERATING CURRENT

The operating current for the external loads depends on the characteristics of the 
battery for self-powering the control panel according to the table alongside.

Current available with
internal battery of 

7.2 Ah

Current available for

 self-powering the system

1200 mA

Current for recharging battery

277 mA

Current available with
internal battery of 

18 Ah

Current available for 

self-powering the system

650 mA

Current for recharging battery

847 mA

INSTALLATION RULES

Installation should be carried out in compliance with the current regulations regarding 
the installation of electrical equipment in the country where the products are installed. 

Cable entry

The mains power supply cables must be inserted using the hole nearest to the 230 
V~ connection terminal block and to which they must be fixed without having been 
consolidated by soldering; they must also have been inserted in advance into an 
additional sheath in order to ensure double insulation.
There must be an over-current circuit breaker with a high breaking capacity (1500 A) 
upstream of the connection to the control panel.

If other holes are used for routing the cables, it is necessary to use cable outlets or 
junction fittings for pipe or sheath constructed with materials of flammability class 
HB or higher.

Earth connection

For the earth connection you need to use the specific terminal located near the trans-
former by the connection of its mains power supply; the metal cover should also be 
earthed, using the Faston terminal.

Caution

: correct earthing protects the control panel and all its devices from faults 

caused by electrical and atmospheric discharges and in particular ensures the integ-
rity of the telecommunications network.

Fuses

F1

: F 3.15A - 250V, located directly on the mains voltage terminals directly at the 

input of the transformer, it protects the low alternating voltage input.

F2

: T 3.15A - 250V, provides protection on the power supply positive output.

F3

: T 3.15A - 250V, provides protection against polarity reversal of the battery.

REGULATORY COMPLIANCE

EN 50131-6.
LV directive. EMC directive.
Standards EN 60950-1, EN 50130-4, EN 61000-6-3.

WEEE - User information

The crossed bin symbol on the appliance or on its packaging indicates 
that the product at the end of its life must be collected separately from 
other waste. The user must therefore hand the equipment at the end of 
its life cycle over to the appropriate municipal centres for the differen-
tiated collection of electrical and electronic waste. As an alternative to 
independent management, you can deliver the equipment you want to 
dispose of to the dealer when purchasing a new appliance of an equiva-
lent type. You can also deliver electronic products to be disposed of that 
are smaller than 25 cm for free, with no obligation to purchase, to elec-
tronics retailers with a sales area of at least 400 m

2

. Proper sorted waste 

collection for subsequent recycling, processing and environmentally 
conscious disposal of the old equipment helps to prevent any possible 
negative impact on the environment and human health while promoting 
the practice of reusing and/or recycling materials used in manufacture.

A

: Terminals for connecting the transformer located under the printed circuit board.

B: 

Terminals for connecting the battery.

C

: Ter - for powering devices.

D

: Terminals for connecting 8-input expansion module 01704.