3.2 1 Output connection

The outputs are not polarised and are isolated from the device's supply voltage by functional isolation (non-reinforced); this allows the connection of output signals 
with reference voltages that differ from the supply voltage of the 21126 control, provided they have SELV power supplies.
Illustrated below are two examples of the wiring layouts that can be achieved. 

Example 1: Connection with output contacts that close to the power supply negative (-) (most frequently used case).

The outputs can be connected to a third-party device with internal pull-up inputs.
The outputs common is to be connected directly to the power supply negative (+).

9-32V

100mA

INPUTS

I2

I4

I6

I8

NC

NC

I1

I3

I5

I7

NC

C IN

O1

O2

O3

O4

O5

O6

O7

NC

C OUT

OUTPUTS

O1

O2

–V

+V

C OUT

UPPER LEFT PUSHBUTTON

  - 

OUT 1

LOWER LEFT PUSHBUTTON

  - 

OUT 2

UPPER CENTRE PUSHBUTTON  - 

OUT 3

LOWER CENTRE PUSHBUTTON - 

OUT 4

UPPER RIGHT PUSHBUTTON  - 

OUT 5

LOWER RIGHT PUSHBUTTON 

 - 

OUT 6

 PROXIMITY - 

OUT 7

IN 1

 - 

UPPER LEFT PUSHBUTTON LED 

IN 2

 - 

LOWER LEFT PUSHBUTTON LED 

IN 3

 - 

UPPER CENTRE PUSHBUTTON LED

IN 4

 - 

LOWER CENTRE PUSHBUTTON LED

 

IN 5

 - 

UPPER RIGHT PUSHBUTTON LED

IN 6

 - 

LOWER RIGHT PUSHBUTTON LED 

IN 7

 - PWM SIGNAL (OPTIONAL)

          

IN 8

 - LOAD ST

ATUS FEEDBACK

MODE (OPTIONAL)

COM. IN

COM OUT

+12VDC

0V

Art. 01831.1

THIRD PARTY 

AUTOMATION SYSTEM 

(FOR EXAMPLE PLC, OR RMS)

OUT

IN

OUT

IN

+V

Vo

Adj.

−V

INPUT:(

输入

):

OUTPUT:(

輸出

):

100-240VAC

0,5A   50/60Hz

12V

N

L

1,25A

10.8~13.8V

Max.1.25A

Max.15Watt

MEAN WELL

“Terminal torque 4.4 Lb-in”

“Terminal torque 4.4 Lb-in”

Connections

Содержание 21126

Страница 1: ...21126 Electronic control with 8 inputs 7 outputs 3 modules Installer manual...

Страница 2: ...2...

Страница 3: ...s 10 4 1 RGB LEDs 10 4 2 Push buttons 10 5 Configuration of the device 11 5 1 Setting the colours of the LEDs 11 5 2 Device setup 11 5 3 Factory reset 12 6 Operation 13 6 1 Display of load status feed...

Страница 4: ...hange the current colour settings of the LEDs Outputs Voltage that can be controlled by the outputs 40 V Current that can be controlled by each individual output 100 mA 3 Connections N B The conductor...

Страница 5: ...om the device s supply voltage by functional isolation non reinforced this allows the connection of input signals with reference voltages that differ from the supply voltage of the 21126 control provi...

Страница 6: ...C IN O1 O2 O3 O4 O5 O6 O7 NC C OUT OUTPUTS V V I1 I2 C IN Example 3 Connection with a signal generator with different voltage references The inputs can be connected directly to a third party device th...

Страница 7: ...loads for example thee coils of large relays or contactors high power LED lights etc Wiring Output 1 Orange Upper left pushbutton Output 2 Yellow Lower left pushbutton Output 3 Green Upper centre push...

Страница 8: ...ply negative 9 32V 100mA INPUTS I2 I4 I6 I8 NC NC I1 I3 I5 I7 NC C IN O1 O2 O3 O4 O5 O6 O7 NC C OUT OUTPUTS O1 O2 V V C OUT UPPER LEFT PUSHBUTTON OUT 1 LOWER LEFT PUSHBUTTON OUT 2 UPPER CENTRE PUSHBUT...

Страница 9: ...with characteristics compatible with the maximum voltage and current values of the 21126 control The outputs common is to be connected directly to the power supply positive 9 32V 100mA INPUTS I2 I4 I...

Страница 10: ...dis played on the cover plate 21663 can be customised using the specific labels 4 2 Pushbuttons When the cover plate is not fitted the 21126 control presents six physical pushbuttons shown in blue and...

Страница 11: ...s not activated or if the signal provided has a pulse width modulation of less than 14 the colours of the LEDs may be set using the following procedure 1 Long press the upper configuration button the...

Страница 12: ...guration procedure without saving any changes made Example The device illustrated below is set to low sensitivity and when in standby the LEDs illuminate with minimum brightness 5 2 2 Setup with rocke...

Страница 13: ...ll remain activated for 60 s or until one the two pushbuttons is pressed again If a change of direction is commanded when the blind is moving both the corresponding outputs remain off for 500 ms befor...

Страница 14: ...ste at the end of its working life The user must take the worn product to a sorted waste center or return it to the retailer when purchasing a new one Products for disposal can be consigned free of ch...

Страница 15: ...Viale Vicenza 14 36063 Marostica VI Italy www vimar com 21126IEN 02 1901...

Отзывы: