DESIGN CRITERI

A - CPVC PIPE

 (See Figures 3-6)

 

(Also refer to the Approval Chart on page 3.)

The Viking COIN

®

 Sprinkler MUST be installed in the upright position.

APPLICATION

For installation in horizontal interstitial concealed spaces constructed of engineered open wood trusses, open bar joist, and non-combustible insulation 

completely filling the upper joist for solid or composite wood joist construction having roof pitch of up to 2/12.

NOTE: 

In order to be considered “non- combustible insulation filled solid wood or composite wood joist construction”, the insulation (including insulation 

provided with a combustible vapor barrier), must completely fill the pockets between the joists to the bottom of the joists, and the insulation must be 

secured in place with metal wire netting. The metal wire netting is intended to hold the insulation in place should the insulation become wetted by the 

operation of the COIN

®

 Sprinklers in the event of a fire.

A. Concealed Space Limitations

The total concealed space is not limited; however, the following must be observed:

• 

Draft curtains (heat collection baffle) or full height walls must be provided to limit the maximum area in order to confine heat of localized detection area 

to 1000 ft

2

 (93 m

2

) or, for solid wood joists and open truss construction with the top chord members on face (not on edge) to 2000 ft

2

 (185 m

2

).

• 

Insulated top chord spaces (on edge) confine heat localized detection area to 2000 ft

2

, non-insulated top chord spaces (on edge) confine heat local-

ized area to 1000 ft

(93 m

2

).

• 

The draft curtain must be at least 1/3 the depth of the concealed space or 8” (200 mm), whichever is greater, for open truss construction, open bar 

joist, and non-combustible insulation filled solid or composite wood joist construction.

• 

The draft curtain must be constructed of material that will not allow heat to escape through or above it; this may be ¼” (6 mm) thick plywood.

• 

Draft curtains are NOT required when sprinkler spacing is up to 14' X 14' (4,3 m X 4,3 m) for solid wood joists or trusses on edge; see Figure 13B. 

• 

Draft curtains are NOT required when sprinkler spacing is up to 16' X 16' (4,9 m X 4,9 m) for truss construction on face (not on edge); see Figure 13A.

• 

Draft curtains are NOT required when using wood truss construction with chords on face and non-combustible insulation is provided to the bottom of 

the trusses (Figure 12).

B. Concealed Space Height

Open Wood Truss and Open Steel Joist Construction (Figure 3):

• 

Maximum height of the space: 60” (1.5 m).

• 

Minimum height: 6” (150 mm)

• 

Maximum roof pitch: 2/12 (9°)

Where applied to pitch roof and flat ceiling, maintain specified clearances from sprinkler deflector to truss and maximum height of pipe run to ceiling or 

non-combustible ceiling insulation in all locations. 

NOTE:

 The sprinkler deflector shall be installed parallel with the roof plane.

Solid wood or composite wood joist with non-combustible filled insulation only (Figure 5):

• 

Maximum depth of concealed space is 60” (1500 mm) from bottom of upper deck joist to top of ceiling joist.

• 

Minimum depth is 6” (152 mm) from bottom of upper deck joist to top of ceiling joist or non-combustible ceiling insulation.

C. System Type

• 

Light Hazard, Wet Pipe System

D. Minimum Density

• 

0.10 gpm/ft

2

 (4.1 mm/min).

E. Spacing of COIN

®

 Sprinklers

• 

Minimum Spacing: 6’-0”(1.8 m)

• 

Maximum Spacing: 16’-0” (4.9 m)

NOTE: 

Minimum spacing does not include additional sprinklers required for obstructions for use of CPVC pipe that includes offsets.

F. Maximum Area of Coverage

• 

256 ft

2

 (24 m

2

)

G. Minimum Operating Pressure

• 

7.0 PSI (0.5 bar)

H. COIN

®

 Sprinkler Deflector Position

The COIN

®

 Sprinkler shall be installed in the upright position. The frame arms must be installed parallel with the pipe.

• 

1-1/2” to 4” (40 - 100 mm) below upper deck for Open Wood Truss and Open Steel Open Joist Construction Using CPVC Pipe (see Figure 3).

• 

1-1/2” to 4” (40 - 100 mm) below non-combustible insulation-filled upper deck for Open Wood Truss and Open Steel Open Joist Construction with 

Using CPVC Pipe (see Figure 4).

• 

1-1/2” to 4” (40 - 100 mm) below non-combustible insulation-filled solid wood joists or composite wood joists (see Figure 5).

(continues on page 5.) 

Содержание VK950

Страница 1: ...and 10 as well as obstructed wood truss construction see Figure 11 When using steel pipe COIN Sprinklers can be applied as a dry system using air or gas as a supervisory medium see Figures 7 11 In certain scenarios draft curtains are NOT required when sprinkler spacing meets either of the following criteria also refer to Design Criteria 14 X 14 4 3 m X 4 3 m for solid wood joists or trusses on edg...

Страница 2: ... Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Screw Brass UNS C36000 Pip Cap and Insert Assembly Copper UNS C11000 and Stainless Steel UNS S30400 Ordering Information Refer to Table 1 4 INSTALLATION Refer to appropriate NFPA Installation Standards 5 OPERATION During a fire condition the heat sensitive liquid in the glass bulb expands causing the glass to shatter releasi...

Страница 3: ...red Temperature Rating Sprinkler Base Part No Size 1 Finishes 2 Temperature Ratings4 Classification Intermediate NPT Inch Description Suffix Nominal Rating Bulb Color Max Ambient Ceiling Temperature1 Suffix 20757 1 2 Brass A 200 F 93 C Green 150 F 65 C E ENT 2 3 JN Corrosion Resistant Coating ENT2 3 Example 20757AE VK950 with Brass Finish and 200 F 93 C Nominal temperature rating This sprinkler is...

Страница 4: ...ction The draft curtain must be constructed of material that will not allow heat to escape through or above it this may be 6 mm thick plywood Draft curtains are NOT required when sprinkler spacing is up to 14 X 14 4 3 m X 4 3 m for solid wood joists or trusses on edge see Figure 13B Draft curtains are NOT required when sprinkler spacing is up to 16 X 16 4 9 m X 4 9 m for truss construction on face...

Страница 5: ...n or 1 3 the depth of the space measured from the top surface of the ceiling to the bottom of the deck above The CPVC pipe can supply the COIN Sprinklers and the ceiling sprinklers below Use all guidelines and installation instructions as specified by the CPVC pipe manufacturers unless specified differently in this data sheet When using 1 DN25 pipe or larger a hanger must be located at the truss n...

Страница 6: ...ervices 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Visit the Viking website for the latest edition of this technical data page www vikinggroupinc com Figure 4 Open Wood Truss and Open Web Steel Joist Construction with Non Combustible Insulation Filling to Bottom of the Top Cord Using CPVC Pipe Cross Section View Figure 3 Open Wood Truss and Open Web Steel Joist Construction Using ...

Страница 7: ...Telephone 269 945 9501 Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Visit the Viking website for the latest edition of this technical data page www vikinggroupinc com Figure 5 Solid Wood or Composite Wood Joist Construction with Non Combustible Insulation Filling Upper Deck Using CPVC Pipe Cross Section View Figure 6 CPVC Piping Installed as a Vertical Riser ...

Страница 8: ... space for open wood truss construction to 2000 ft2 185 m2 with their top chord members on face not on edge and 2000 ft2 185 m2 for solid wood joists Insulated top chord spaces on edge confine heat localized detection area to 2000 ft2 185 m2 non insulated top chord spaces on edge confine heat localized area to 1 000 ft2 93 m2 The draft curtain may be constructed of 6 mm thick plywood to prevent he...

Страница 9: ...omposite wood joists is 1000 ft2 93 m2 For dry pipe systems 1 The remote area for open wood truss construction or open bar joist construction with the top chord members on face not on edge is 1000 ft2 93 m2 or 6 sprinklers whichever is greater See Table 2 Draft curtains are NOT required when sprinkler spacing is up to 16 X 16 4 9 m X 4 9 m The remote area for this application is the same as above ...

Страница 10: ...01 Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Visit the Viking website for the latest edition of this technical data page www vikinggroupinc com Figure 8 Solid Wood or Composite Wood Joist Construction with Non Combustible Insulation Filled Upper Deck Steel Pipe Cross Sectional View Figure 9 Unobstructed Open Wood Truss and Open Steel Bar Joist Steel Pipe Cross ...

Страница 11: ...echnical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Visit the Viking website for the latest edition of this technical data page www vikinggroupinc com Figure 11 Obstructed Wood Truss Construction Steel Pipe Cross Sectional View Figure 10 Open Wood Truss and Open Web Steel Joist Construction with Non Combustible Insulation Filling to Bottom of the Top Cord Using Steel Pipe...

Страница 12: ...stings MI 49058 Telephone 269 945 9501 Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Visit the Viking website for the latest edition of this technical data page www vikinggroupinc com Figure 12 Wood Truss Construction with Chords on Face and Non combustible Insulation Provided to the Bottom of the Trusses CPVC and Steel Pipe Cross Section View ...

Страница 13: ... Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Visit the Viking website for the latest edition of this technical data page www vikinggroupinc com Figure 13A Trusses on Face Figure 13B Trusses on Edge 1 1 2 38 mm 1 1 2 38 mm On Edge On Face Example of Typical 2x4 Construction Refer to Design Critera Example of Typical 2x4 Construction Refer to Design Critera 3 1 2 8...

Страница 14: ...om of Obstruction Y 1 0 300 mm 0 0 mm 1 0 to 1 6 300 mm to 450 mm 0 0 mm 1 6 to 2 0 450 mm to 600 mm 1 25 mm 2 0 to 2 6 600 mm to 750 mm 1 25 mm 2 6 to 3 0 750 mm to 900 mm 1 75 mm 3 0 to 3 6 900 mm to 1 1 m 3 75 mm 3 6 to 4 0 1 1 m to 1 2 m 3 75 mm 4 0 to 4 6 1 2 m to 1 4 m 5 125 mm 4 6 to 5 0 1 4 m to 1 5 m 7 175 mm Distance from Sprinkler to Side of Obstruction X Maximum Allowable Distance of D...

Страница 15: ... the sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately Note Installing glass bulb sprinklers in direct sunlight ultraviolet light may af...

Страница 16: ...uctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16 4 Class 125 even at branch line ends The threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth This prevents co...

Страница 17: ...ther To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Retain a protective cap or shield in the spare sprinkler cabinet 5 For flush style sprinklers the ceiling ring can now be installed onto the sprinkler body Align the ceiling ring with the sprinkle...

Страница 18: ...Prior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2a For frame style sprinklers use the special sprinkler wrench to remove the old sprinkler by turning it counterclockwise to unthread it from the...

Страница 19: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Страница 20: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Страница 21: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Страница 22: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 23: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 24: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 25: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 26: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: