ESFR PENDENT SPRINKLER 

UL: SPECIFIC APPLICATION ESFR SPRINKLER 

FM: STORAGE SPRINKLER

NFPA: SPECIAL SPRINKLER  

VK514 (K28.0)

TECHNICAL BULLETIN

Page 3 of 6

Form No. F_102422      Rev 01     October 2022

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

D.  When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system description and/

or valve instructions. Prior to removing the system from service, notify all Authorities Having Jurisdiction. Consideration should 

be given to employment of a fire patrol in the affected area.

E.  Remove the system from service, drain all water, and relieve all pressure on the piping.
F.  Using the special sprinkler wrench, remove the old sprinkler and install the new unit. Care must be taken to ensure that the re-

placement sprinkler is the proper model and style, with the correct orifice size, temperature rating, and response characteristics. 

A fully stocked spare sprinkler cabinet should be provided for this purpose.

G.  Place the system back in service and secure all valves. Check the replaced sprinklers and repair all leaks.
H.  Sprinkler systems that have been subject to a fire must be returned to service as soon as possible. The entire system must 

be inspected for damage and repaired or replaced as necessary. Sprinklers that have been exposed to corrosive products of 

combustion, but have not operated, should be replaced. Refer to the Authorities Having Jurisdiction for minimum replacement 

requirements.

8.  AVAILABILITY

The Viking Model VK514 Sprinkler is available through a network of domestic and international distributors. See The Viking 

Corporation web site for the closest distributor or contact The Viking Corporation.

9.  GUARANTEE

For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

TABLE 2: ORDERING INFORMATION

Instructions: Using the sprinkler base part number,

 (1) add the suffix for the desired Finish

 (2) add the suffix for the desired Temperature Rating. 

Sprinkler 

Base Part 

No.

Size

1: Finishes

2: Temperature Ratings

1

NPT

Inch

BSPT

mm

Description Suffix

Nominal 

Rating

Frame 

Paint 

Color

Temperature 

Classification

Max. Ambient Ceiling 

Temperature

2

Suffix

19591

1

--

Brass

A

165 °F (74 °C)

None

Ordinary

100 °F (38 °C)

C

19592

--

25

205 °F (96 °C)

White

Intermediate

150 °F (65 °C)

E

22894

1

--

Example

: 19591AC = VK514 with Brass Finish and 165 °F (74 °C) Nominal temperature 

rating. This sprinkler is to be installed into an area with a maximum ambient tempe-

rature of 100 °F (38 °C) meaning if the area will experience temperatures above the 

maximum ambient rating, you shall use a higher temperature-rated sprinkler.

22958

--

25

Accessories

Sprinkler Wrenches (see Figure 1):

Standard Wrench: Part No. 13635W/B (double-ended wrench - Use Side B ONLY.)

Sprinkler Cabinet:

Up to 6 sprinklers: Part number 01731A

Footnotes

1. 

The sprinkler temperature rating is stamped on the deflector.

2. 

Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having 

Jurisdiction. Refer to specific installation standards.

Содержание VK514

Страница 1: ...torage materials including Encapsulated or unencapsulated Class I II III and IV commodities UL Listed for protection of cartoned nonexpanded Group A plastic commodities FM Approved for protection of cartoned unexpanded plastic commodities Refer the Approval Chart and Commodity Selection and Design Criteria Overview for Listing and Approval requirements that must be followed The terms nonexpanded a...

Страница 2: ...sequent leakage or impairment of the sprinkler E After installation the entire sprinkler system must be tested The test must be conducted to comply with the Installation Standards Make sure the sprinkler has been properly tightened If a thread leak occurs normally the unit must be removed new pipe joint compound or tape applied and then reinstalled This is due to the fact that when the joint seal ...

Страница 3: ... products of combustion but have not operated should be replaced Refer to the Authorities Having Jurisdiction for minimum replacement requirements 8 AVAILABILITY The Viking Model VK514 Sprinkler is available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 9 GUARANTEE For details of warran...

Страница 4: ...PT 28 0 404 3 3 16 81 A1 22894 VK514 1 NPT 28 0 404 3 3 16 81 A1 A1 22958 VK514 25 mm BSPT 28 0 404 3 3 16 81 A1 A1 Approved Temperature Ratings A 165 F 74 C and 205 F 96 C Approved Finish 1 Brass Footnotes 1 Base part number shown For complete part number refer to the price list 2 Metric K Factor measurement shown is when pressure is measured in bar When pressure is measured in kPa divide the met...

Страница 5: ...of 4 in 102 mm from walls but no more than 1 2 the allowable distance permitted between sprinklers Deflector distance measured from ceiling to sprinkler deflector Minimum of 36 in 914 mm Sprinkler installation from ceiling For all building heights 6 14 in 152 356 mm Maximum Ceiling Height 48 ft 14 6 m Maximum Storage Height 43 ft 13 1 m Storage Arrangement Single and double row rack storage no ope...

Страница 6: ...g Sprinkler Installation Guidelines As per FM 2 0 DS 2 0 Installation Guidelines for Automatic Sprinklers with the following exception Vertical distance from underside of the ceiling to the centerline of the sprinkler s thermal element no more than 13 inches 325 mm As per FM 2 0 DS 2 0 Installation Guidelines for Automatic Sprinklers with the following exception Vertical distance from underside of...

Отзывы: