ESFR PENDENT SPRINKLER 

VK503 (K16.8)

TECHNICAL DATA

Page 5 of 6

Form No. F_120106    18.10.11    Rev 18.2

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

Approval Chart 1 (UL)

ESFR Pendent Sprinkler VK503 

Maximum 175 PSI (12 bar) WWP

Base Part 

Number

1

SIN

NPT Thread Size

Nominal 

K-Factor

Overall Length

Listings and Approvals

3,4 

(Refer also to Design Criteria on page 4.)

Inches

NPT

mm

BSPT

U.S.

metric

2

Inches

mm

cULus

5

NYC

6

14073

VK503

3/4”

--

16.8

242

2-7/8

73

A1

A1

--

--

14818

VK503

--

20 mm

16.8

242

2-7/8

73

A1

A1

--

--

19856

VK503

--

20 mm

16.8

242

2-7/8

73

--

--

--

B1

20372

VK503

--

20 mm

16.8

242

2-7/8

73

--

--

--

B1

Approved Temperature Ratings

A - 165 °F (74 °C) and 205 °F (96 °C)

B - 165 °F (74 °C)

Approved Finish

1 - Brass

Footnotes

1

 Base part number shown. For complete part number, refer to the price list.

2

 Metric K-Factor measurement shown is when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-Factor shown by 10.0.

3

 This chart shows listings and approvals available at the time of printing. Other approvals may be in process. 

4

 Refer to the latest standards of NFPA 13.

Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.

6

 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 41.

Approval Chart 2 (FM)

ESFR Pendent Sprinkler VK503 

Maximum 175 PSI (12 bar) WWP

Base Part 

Number

1

SIN

Thread Size

Nominal K-Factor

Overall Length

FM Approvals

3,4 

(Refer also to Design Criteria below.)

Inches 

NPT

mm 

BSPT

U.S.

metric

2

Inches

mm

14073

VK503

3/4”

--

16.8

242

2-7/8

73

A1

14818

VK503

--

20 mm

16.8

242

2-7/8

73

A1

Approved Temperature Ratings

A - 165 °F (74 °C) and 205 °F (96 °C)

Approved Finish

1 - Brass

Footnotes

1

 Base part number shown. For complete part number, refer to the price list.

2

 Metric K-Factor measurement shown is when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-Factor shown by 10.0.

3

 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. 

4

 FM Approved as a quick response pendent 

Non-Storage

 sprinkler and also FM Approved as a quick response pendent 

Storage

 sprinkler. Refer to 

Design Criteria below.

Содержание VK503

Страница 1: ...wed In addition some storage arrangements of rolled paper aerosols and rub ber tires may be protected by Viking ESFR Pendent Sprinkler VK503 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Successfully meets UL 1767 test standard and compliance program for ESFR sprinklers installed in rack storage with high clearances to ceiling 20 ft or greater FM Approved Class 2027 NYC Approved MEA 89 92 E ...

Страница 2: ...ing container Never install sprinklers that have been dropped or damaged in any way Such sprinklers should be destroyed immediately NOTE Wet pipe systems must be provided with adequate heat B The sprinklers must be installed after the piping is in place to prevent mechanical damage Before installing be sure to have the appropriate sprinkler model and style with the correct orifice size temperature...

Страница 3: ...llation Standards e g NFPA 25 and the Authorities Having Jurisdiction for the specified period of time after which testing and or replacement is required Sprinklers that have operated cannot be reassembled or reused but must be replaced When replacing sprinklers use only new sprinklers C The sprinkler discharge pattern is critical for proper fire protection Therefore nothing should be hung from at...

Страница 4: ...cation Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White Sprinkler Finish Brass Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority ...

Страница 5: ...is measured in kPa divide the metric K Factor shown by 10 0 3 This chart shows listings and approvals available at the time of printing Other approvals may be in process 4 Refer to the latest standards of NFPA 13 5 Listed by Underwriters Laboratories Inc for use in the U S and Canada 6 Accepted for use City of New York Department of Buildings MEA Number 89 92 E Vol 41 Approval Chart 2 FM ESFR Pend...

Страница 6: ... Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Rolled Paper Storage Refer to the standard Refer to NFPA 13 Refer to FM 8 21 Flammable Liquid Storage Refer to the standard Refer to NFPA 30 Refer to FM 7 29 Aerosol Storag...

Отзывы: