TECHNICAL DATA

Page 1 of 6

Form No. F_120106    18.10.11    Rev 18.2

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

1.  DESCRIPTION

Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK503 is a fast 

response fusible element type sprinkler designed for early fire suppression. With a 

16.8 (242 metric*) nominal K-Factor and special deflector, this sprinkler produces large, 

high-momentum water droplets in a hemispheric pattern below the deflector. This per-

mits penetration of the fire plume and direct wetting of the burning fuel surface while 

cooling the atmosphere early in the development of a high-challenge fire.
Viking Sprinkler VK503 may be used in the protection of ordinary types of storage. 

However, it is primarily intended to protect the following types of storage, which tend 

to produce severe-challenge fires: palletized and solid pile storage and single, double, 

multiple row, and portable open rack storage (no open-top containers or solid shelves).
Viking ESFR Pendent Sprinkler VK503 provides protection of most common storage 

materials, including: 

--Encapsulated or unencapsulated Class I, II, III, and IV commodities*.

--Cartoned and uncartoned unexpanded plastics*.

--Cartoned expanded plastics*.

* Refer to the Approval Charts and Commodity Selection and Design Criteria Overview for cULus 

Listing and FM Approval requirements that must be followed.

In addition, some storage arrangements of rolled paper, aerosols, and rub-

ber tires may be protected by Viking ESFR Pendent Sprinkler VK503.

2.  LISTINGS AND APPROVALS

cULus Listed: 

Category VNWH

Successfully meets UL 1767 test standard and compliance 

program for ESFR sprinklers installed in-rack storage with 

high clearances to ceiling (20 ft or greater)

FM Approved:

 Class 2027 

NYC Approved:

 MEA 89-92-E, Volume 41

CCCF Approved: 

Approved by the China Certification Center for 

Fire Products (CCCF)

Refer to the Approval Charts and Commodity Selection and Design 

Criteria Overview for cULus Listing and FM Approval requirements 

that must be followed.

3.  TECHNICAL DATA

Specifications:

Available since 2007.

Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi 

(34.5 bar).

Thread size: 3/4” NPT or 20 mm BSPT 

Nominal K-Factor: 16.8 U.S. (242 metric*)

* Metric K-factor measurement shown is when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

Overall Length: 2-7/8” (73 mm)

Deflector Diameter: 1-3/4” (44.5 mm)

Covered by one or more of the following patents: US5,829,532; US6,059,044; US6,336,509; US6,502,643; US6,868,917; AU722593; GB2336777

Material Standards:

Frame Casting: Brass UNS-C84400 

Deflector: Phosphor Bronze UNS-C51000

Seat and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Compression Screw: Stainless Steel UNS-S31603

Replaces Form No. F_120106 Rev 18.1 

(Replaced design criteria tables; added P65 Warning.)    

TABLE 1

SPRINKLER GENERAL INFORMATION

Item

Description

Sprinkler Identification 

Number (SIN)

VK503

K-factor, gpm/psi

½

 (lpm/bar

½

)

16.8 (242) 

Thread Size

3/4” NPT (20 mm BSPT)

Sprinkler Orientation

Pendent

Maximum Working Pressure

175 psi (12 bar)

Содержание VK503

Страница 1: ...wed In addition some storage arrangements of rolled paper aerosols and rub ber tires may be protected by Viking ESFR Pendent Sprinkler VK503 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Successfully meets UL 1767 test standard and compliance program for ESFR sprinklers installed in rack storage with high clearances to ceiling 20 ft or greater FM Approved Class 2027 NYC Approved MEA 89 92 E ...

Страница 2: ...ing container Never install sprinklers that have been dropped or damaged in any way Such sprinklers should be destroyed immediately NOTE Wet pipe systems must be provided with adequate heat B The sprinklers must be installed after the piping is in place to prevent mechanical damage Before installing be sure to have the appropriate sprinkler model and style with the correct orifice size temperature...

Страница 3: ...llation Standards e g NFPA 25 and the Authorities Having Jurisdiction for the specified period of time after which testing and or replacement is required Sprinklers that have operated cannot be reassembled or reused but must be replaced When replacing sprinklers use only new sprinklers C The sprinkler discharge pattern is critical for proper fire protection Therefore nothing should be hung from at...

Страница 4: ...cation Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White Sprinkler Finish Brass Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority ...

Страница 5: ...is measured in kPa divide the metric K Factor shown by 10 0 3 This chart shows listings and approvals available at the time of printing Other approvals may be in process 4 Refer to the latest standards of NFPA 13 5 Listed by Underwriters Laboratories Inc for use in the U S and Canada 6 Accepted for use City of New York Department of Buildings MEA Number 89 92 E Vol 41 Approval Chart 2 FM ESFR Pend...

Страница 6: ... Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Rolled Paper Storage Refer to the standard Refer to NFPA 13 Refer to FM 8 21 Flammable Liquid Storage Refer to the standard Refer to NFPA 30 Refer to FM 7 29 Aerosol Storag...