background image

BULLETIN

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

CARE AND HANDLING 

OF SPRINKLERS

Page 1 of 4

Form No. F_091699     18.10.11    Rev 16.1.P65

SPRINKLERS ARE FRAGILE - HANDLE WITH CARE!

General Handling and Storage:

• 

Store sprinklers in a cool, dry place.

• 

Protect sprinklers during storage, transport, handling, and after installation.

• 

Use the original shipping containers. DO NOT place sprinklers loose in boxes, bins, 

or buckets.

• 

Keep sprinklers separated at all times. DO NOT allow metal parts to contact sprinkler 

operating elements.

For Pre-Assembled Drops:

• 

Protect sprinklers during handling and after installation.

• 

For recessed assemblies, use the protective sprinkler cap (Viking Part Number 10364).

Sprinklers with Protective Shields or Caps:

• 

DO NOT remove shields or caps until after sprinkler installation and there no longer is 

potential for mechanical damage to the sprinkler operating elements.

• 

Sprinkler shields or caps MUST be removed BEFORE placing the system in 

service!

• 

Remove the sprinkler shield by carefully pulling it apart where it is snapped together.

• 

Remove the cap by turning it slightly and pulling it off the sprinkler.

Sprinkler Installation:

• 

DO NOT use the sprinkler deflector or operating element to start or thread the sprinkler 

into a fitting.

• 

Use only the designated sprinkler head wrench!

 Refer to the current sprinkler tech-

nical data page to determine the correct wrench for the model of sprinkler used.

• 

DO NOT install sprinklers onto piping at the floor level.

• 

Install sprinklers after the piping is in place to prevent mechanical damage.

• 

DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings, pipe, 

or couplings in close proximity to sprinklers. Sprinklers can be damaged from direct or 

indirect impacts.

• 

DO NOT attempt to remove drywall, paint, etc., from sprinklers.

• 

Take care not to over-tighten the sprinkler and/or damage its operating parts! 

Maximum Torque:  

1/2” NPT:   14 ft-lbs. (19.0 N-m)        
3/4” NPT:   20 ft-lbs. (27.1 N-m)         
1” NPT:   30 ft-lbs. (40.7 N-m)

 WARNING

Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed. Never install sprinklers 

that have been dropped, damaged, or exposed to temperatures exceeding the maximum ambient temperature allowed. Sprinklers that 

have been painted in the field must be replaced per NFPA 13. Protect sprinklers from paint and paint overspray in accordance with 

the installation standards. Do not clean sprinklers with soap and water, ammonia, or any other cleaning fluid. Do not use adhesives 

or solvents on sprinklers or their operating elements.

Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance 

instructions. For additional product and system information Viking data pages and installation instructions are available on 

the Viking Web site at www.vikinggroupinc.com.

CORRECT

(Original container used)

INCORRECT

(Placed loose in box)

CORRECT

(Protected with caps)

INCORRECT

(Protective caps not used)

CORRECT

(Piping is in place at the 

ceiling)

INCORRECT

(Sprinkler at floor level)

CORRECT

(Special installation 

wrenches)

INCORRECT

(Designated wrench not 

used)

Replaces Form No. F_091699 Rev 16.1

(Added P65 Warning)

Содержание VK4651

Страница 1: ...2 LISTINGS AND APPROVALS cULus Listed Category VNIV Refer to the Approval Charts and Design Criteria for cULus Listing requirements that must be followed 3 TECHNICAL DATA Specifications Minimum Operating Pressure 7 psi 0 5 bar Maximum Working Pressure 175 psi 12 bar Factory tested hydrostatically to 500 psi 34 5 bar Thread size 1 2 15 mm NPT or 15 mm BSPT Nominal K Factor 4 2 U S 57 metric Glass b...

Страница 2: ...te refer to Table 2 Example 23233AE 200 F 93 C Temperature Rated Sprinkler with a standard Brass finish Sprinkler Base Part No Size 1 Finishes 2 Temperature Ratings NPT Inch BSPT mm Description Suffix1 Sprinkler Temperature Classification Nominal Rating Bulb Color Max Ambient Ceiling Temperature2 Suffix 23233 1 2 Brass A Oridinary 155 F 68 C Red 100 F 38 C B 23235 15 ENT 3 4 JN Intermediate 175 F ...

Страница 3: ...23179 3 5 16 84 Square 23482 3 5 16 84 Square Bright Brass B 231934 2 3 4 70 Stainless Steel Round 23455 2 3 4 70 Stainless Steel Round Antique Brass B A Brushed Brass B B 231834 3 5 16 84 Stainless Steel Round 23473 3 5 16 84 Stainless Steel Round Brushed Copper E B Painted White M W Painted Ivory M I Painted Black M B 3 Temperature Rating Matrix1 2 Cover Plate Nominal Rating Required Temperature...

Страница 4: ...nal approvals 4 Listed by Underwriter s Laboratories for use in the U S and Canada 5 The 135 F 57 C covers have an orange label The 165 F 74 C covers have a white label 6 Other paint colors are available on request with the same listings as the standard paint colors Listings and approvals apply for any paint manufacturer Contact Viking for additional information 7 cULus Listed as corrosion resista...

Страница 5: ...ta page www vikinggroupinc com Page 5 of 8 Form No F_040320 21 12 02 Rev 21 3 Figure 2 Identification of Custom Paint Figure 3 Square Cover Assembly All custom color painted cover plates will have an identifying label affixed to the inside of the cover that indicates the custom color and will have a representative sample a paint dot of the paint on the label F A C T O R Y A P PLIED CUSTOM P A I N ...

Страница 6: ...2 13 mm If the bottom of the cover is flush with the surface of the ceiling when installed the sprinkler adapter cup will be recessed 1 2 15 mm See Figure 5 Figure 4 Sprinkler Dimensions 3 76 mm 21 4 57 mm 1 2 NPT or BSPT Nominal pipe engagement 7 16 11 mm Install the sprinkler so the finished surface of the ceiling lines up within the marked 1 2 13 mm range on the protective cap A Figure 5 Sprink...

Страница 7: ...n occur if the proper wrench is not used Other sprinkler wrenches available from Viking may fit into the sprinkler adapter cup however only the wrenches shown here are designed to properly install this sprinkler Step 2 Rotate the wrench slightly in either direction until the tines on the wrench D line up with the vent openings E on the adapter cup and lock into place NOTE A leak tight seal must be...

Страница 8: ...n of this technical data page www vikinggroupinc com Page 8 of 8 Form No F_040320 21 12 02 Rev 21 3 Replaces Form No F_040320 Rev 21 2 Updated wrench drive Figure 8 Installing the Cover Plate Install the cover plate by inserting the adpater into the adapter cup and pushing or threading into place depending on style Snug the cover plate in place by rotating clockwise Ensure the cover plate is flush...

Страница 9: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 10: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 11: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 12: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 13: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Страница 14: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Страница 15: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Страница 16: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: