VK3001 QUICK RESPONSE 

UPRIGHT SPRINKLER (K5.6)

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Page 3 of 6

Form No. F_110420    Rev 22.1    February 22, 2022

Figure 2: Sprinkler Dimensions

7/16” (11 mm) 

Nominal Pipe 

Engagement

1-15/16”  

(49 mm) 

1/2” NPT or 

15 mm BSPT 

TABLE 1: ORDERING INFORMATION

Instructions: Using the sprinkler base part number,

 (1) add the suffix for the desired Finish

 (2) add the suffix for the desired Temperature Rating. 

Sprinkler 

Base Part 

Number

Size

1: Finishes

2: Temperature Ratings

NPT

Inch

BSPT

mm

Description

Suffix

1

Nominal Rating

Bulb Color Max. Ambient Ceiling 

Temperature

2

Suffix

23869

1/2

--

Brass

A

135 °F (57 °C)

Orange

100 °F (38 °C)

A

23881

--

15

Chrome

F

155 °F (68 °C)

Red

100 °F (38 °C)

B

White Polyester 

3,5

M-/W

175 °F (79 °C)

Yellow

150 °F (65 °C)

D

Black Polyester 

3,5

M-/B

200 °F (93 °C)

Green

150 °F (65 °C)

E

ENT 

3,4,5

JN

286 °F (141 °C)

Blue

225 °F (107 °C)

G

OPEN

--

--

Z

Example

: 23869MB/W = VK3001 with white polyester finish and 155 °F (68 °C) nominal temperature rating. This sprinkler is to be 

installed into an area with a maximum ambient temperature of 100 °F (38 °C) meaning if the area will experience temperatures above 

the maximum ambient rating, you shall use a higher temperature-rated sprinkler.

Accessories
Sprinkler Wrenches (see Figure 1):

Standard (straight) Wrench: Part number 23559MB.

Sprinkler Cabinet:

A.  Up to 6 sprinklers: Part number 01724A

B.  6-12 sprinklers: Part number 01725A

Footnotes

1. 

Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.

2. 

Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having 

Jurisdiction. Refer to specific installation standards.

3. 

UL Listed as corrosion resistant.

4. 

FM Approved as corrosion resistant.

5. 

The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and 

do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed 

environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.

6. 

UL Listed for 250 PSI (17 bar) WWP.

Figure 1: Sprinkler Wrench

Top View

Содержание VK3001

Страница 1: ...0 5 bar Rated to UL 250 PSI 17 bar WWP FM CE LBCP and VdS 175 PSI 12 bar WWP Factory tested hydrostatically to 500 PSI 34 5 bar Thread size 1 2 NPT 15 mm BSPT Nominal K factor 5 6 U S 80 6 metric Glass bulb fluid temperature rated to 65 F 55 C Metric K factor measurement shown is in bar When pressure is measured in kPa divide the metric K factor shown by 10 0 Material Standards Sprinkler Body Bras...

Страница 2: ...his technical data page www vikinggroupinc com Page 2 of 6 Form No F_110420 Rev 22 1 February 22 2022 6 INSPECTIONS TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking Sprinklers are available through a network of domestic and international distributors See the website for the closest distributor or contact Viking 8 GUARANTEE For details...

Страница 3: ...rature rating This sprinkler is to be installed into an area with a maximum ambient temperature of 100 F 38 C meaning if the area will experience temperatures above the maximum ambient rating you shall use a higher temperature rated sprinkler Accessories Sprinkler Wrenches see Figure 1 Standard straight Wrench Part number 23559MB Sprinkler Cabinet A Up to 6 sprinklers Part number 01724A B 6 12 spr...

Страница 4: ...175 PSI 12 bar Additional Listings and Approvals Maximum WWP 175 PSI 12 bar CE6 LPCB7 VdS8 23869 1 2 B1 A1 A1 23881 15 B1 A1 A1 Approved Temperature Ratings A 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C and 286 F 141 C B 155 F 68 C 175 F 79 C 200 F 93 C and 286 F 141 C Approved Finishes 1 Brass Chrome White Polyester 3 4 Black Polyester 3 4 and ENT 4 5 Footnotes 1 Base Part number is shown For com...

Страница 5: ...ick Response Upright Sprinkler is FM Approved as quick response Non Storage upright sprinkler as indicated in the FM Approval Guide For specific application and installation requirements reference the latest applicable FM Loss Prevention Data Sheets including Data Sheet 2 0 FM Global Loss Prevention Data Sheets contain guidelines relating to but not limited to minimum water supply requirements hyd...

Страница 6: ...isit the Viking website for the latest edition of this technical data page www vikinggroupinc com Page 6 of 6 Form No F_110420 Rev 22 1 February 22 2022 Replaces page F_110420 Rev 21 2 Added LPCB and VdS details Figure 3 Installation Frame arms must be parallel to the pipe 1 2 1 Carefully slide the wrench onto the wrench flats 2 Install the sprinkler into the pipe fitting NOTE The sprinkler frame ...

Страница 7: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 8: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 9: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 10: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 11: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Страница 12: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Страница 13: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Страница 14: ...he sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately Note Installing glass bulb sprinklers in direct sunlight ultraviolet light may affe...

Страница 15: ...uctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16 4 Class 125 even at branch line ends The threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth This prevents co...

Страница 16: ...ther To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Retain a protective cap or shield in the spare sprinkler cabinet 5 For flush style sprinklers the ceiling ring can now be installed onto the sprinkler body Align the ceiling ring with the sprinkle...

Страница 17: ...Prior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2a For frame style sprinklers use the special sprinkler wrench to remove the old sprinkler by turning it counterclockwise to unthread it from the...

Страница 18: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Страница 19: ...ssories painting plating coating or modification may render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation Refer to the Authority Having Jurisdiction prior to installation 2 GENERAL INFORMATION A potential product performance issue may exist when listed products are combined with unlisted product s that have not been evaluated...

Отзывы: