background image

MICROFAST

®

 QUICK 

RESPONSE FUSIBLE 

ELEMENT UPRIGHT 

SPRINKLER VK328 (K4.2)

TECHNICAL DATA

Page 1 of 3

Form No. F_071114     21.03.05    Rev 21.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

1.  DESCRIPTION

The Viking Microfast

®

 Quick Response Upright Fusible Element Sprinkler 

VK328 is a small, thermosensitive, solder link spray sprinkler available 

in several different finishes and temperature ratings to meet design 

requirements.  The special Polyester and Electroless Nickel PTFE (ENT) 

coatings can be used in decorative applications where colors are desired. 

In addition, The ENT coating has been investigated for installation in 

corrosive environments and is listed/approved as indicated in the Approval 

Chart(s).

2.  LISTINGS AND APPROVALS

cULus Listed: 

Category VNIV

Refer to Approval Chart and Design Criteria for cULus Listing requirements that 

must be followed.

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar)* 

Maximum Working Pressure: 175 psi (12 bar) wwp. 

Factory tested hydrostatically to 500 psi (34.5 bar)

Testing: U.S.A. Patent No. 4,831,870

Thread size: 1/2” NPT, 15 mm BSPT

Nominal K-Factor: 4.2 U.S. (57 metric**)

Overall Length: 2-3/16” (56 mm)

 *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE 

Approvals ONLY is 5 psi (0.35 bar). 

Material Standards:

Frame Casting: Brass UNS-C84400

Deflector: Brass UNS-C23000 or Copper UNS-C19500

Bushing: Brass UNS-C36000

Fusible Element Assembly: Nickel Alloy

Trigger and Support: UNS-S31603

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Seat and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400

Screw: Brass UNS-C36000

For Polyester Coated Sprinklers: Belleville Spring-Exposed

For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw-ENT Plated, Pip Cap-ENT Coated

Ordering Information:

 (Also refer to the current Viking price list.)

Order Viking Microfast

®

 Quick Response Fusible Element Upright Sprinkler VK328 by first adding the appropriate suffix for the 

sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. 

Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B and ENT = JN

Temperature Suffix: 165 °F (74 °C) = C, 205 °F (96 °C) = E, and 280 °F (138 °C)

For example, sprinkler VK328 with a 1/2” NPT thread, Brass finish and a 165 °F (74 °C) temperature rating = Part No. 13958AB

Available Finishes And Temperature Ratings: 

Refer to Table 1.

Accessories:

 (Also refer to the Viking website.)

Sprinkler Wrench: 

Standard Wrench: Part No. 21475M/B (available since 2017)

 

Sprinkler Cabinets:

A. Six-head capacity: Part No. 01724A (available since 1971)

B. Twelve-head capacity: Part No. 01725A (available since 1971)

4.  INSTALLATION

Refer to appropriate NFPA Installation Standards.

Replaces Form No. F_071114 Rev 20.1

(Removed bushed part numbers)

Содержание MICROFAST VK328

Страница 1: ...a minimum of 7 psi 0 5 bar The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi 0 35 bar Material Standards Frame Casting Brass UNS C84400 Deflector Brass UNS C23000 or Copper UNS C19500 Bushing Brass UNS C36000 Fusible Element Assembly Nickel Alloy Trigger and Support UNS S31603 Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Seat and Insert A...

Страница 2: ...TURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White High 280 F 138 C 225 F 107 C Blue Sprinkler Finishes Brass Chrome White Polyester5 Black Polyester5 and ENT3 4 Corrosion Resistant Sprinkler Coatings ENT3 4 Footnotes ...

Страница 3: ...are available on request with the same Listings and Approvals as the standard colors 6 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied with hydraulically calculated wet systems only 7 cULus Listed as corrosion resistant DESIGN CRITERIA UL Also refer to Approval Chart 1 above cULus Listing Requirements Quick Response Fusible Eleme...

Страница 4: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 5: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 6: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 7: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 8: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: