MICROFAST

®

 QUICK 

RESPONSE FUSIBLE 

ELEMENT CONVENTIONAL 

SPRINKLER VK311 (K5.6)

TECHNICAL DATA

Page 3 of 3

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

Form No. F_022614     18.11.05     Rev 17.1.P65

Approval Chart 1 (UL)

Microfast

®

 Quick Response Fusible Element Conventional Sprinkler VK311

 

Maximum 175 PSI (12 bar) WWP

Base Part 

Number

1

SIN

Thread Size

Nominal K-Factor

Overall Length

Listings and Approvals

(Refer also to Design Criteria below.)

NPT

BSP

U.S.

metric

2

Inches

mm

cULus

4

Conventional-Standard Orifice

19392

VK311

1/2”

15 mm

5.6

80.6

2-3/16

56

A1

NOTICE - Product Below - Limited Availability (Contact Local Viking Office)

13952

VK311

1/2”

15 mm

5.6

80.6

2-3/16

56

A1

Approved Temperature Ratings

A - 165 °F (74 °C), 205 °F (96 °C), and 280 °F (138 °C)

Approved Finishes

1 - Brass, Chrome, White Polyester

5

, and Black Polyester

5

Footnotes

1

 Base part number is shown. For complete part number, refer to Viking’s current price schedule.

2

 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

3

 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.

4

 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.

5

 Other colors are available on request with the same Listings and Approvals as the standard colors.

DESIGN CRITERIA - UL

 

(Also refer to Approval Chart 1 above.)

cULus Listing Requirements:

 

Quick Response Fusible Element Conventional (Old Style) Sprinkler VK311 is cULus Listed as indicated in the Approval Chart for installation in ac-

cordance with the latest edition of NFPA 13 for old style (conventional) sprinklers.

• 

Designed for use in Light and Ordinary Hazard occupancies 

• 

The sprinkler installation rules contained in NFPA 13 for standard spray old style (conventional) sprinklers must be followed. 

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 

for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest 

edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and 

also with the provisions of governmental codes, ordinances, and standards, whenever applicable. 

Replaces form F_071614 Rev. 17.1

(Added P65 Warning.)

Содержание MICROFAST VK311

Страница 1: ...r When pressure is measured in kPa divide the metric K factor shown by 10 0 Material Standards Frame Casting Brass UNS C84400 or QM Brass Deflector Brass UNS C26000 Fusible Element Assembly Nickel Alloy Trigger and Support Stainless Steel UNS S31600 Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Seat and Insert Assembly Copper UNS C11000 and Stainless Steel UNS...

Страница 2: ...ernational distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperatu...

Страница 3: ...ured in Bar When pressure is measured in kPa divide the metric K factor shown by 10 0 3 This table shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals 4 Listed by Underwriters Laboratories Inc for use in the U S and Canada 5 Other colors are available on request with the same Listings and Approvals as the standard colors DESIG...

Страница 4: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 5: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 6: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 7: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 8: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: