MICROFAST

®

 QUICK 

RESPONSE CONVENTIONAL 

SPRINKLER VK310 (K5.6)

TECHNICAL DATA

Page 3 of 3

Form No. F_022514    18.11.05    Rev 18.1.P65

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

Approval Chart 1 (UL)

Microfast

®

 Quick Response

 

Conventional Sprinkler VK310

 

Maximum 175 PSI (12 bar) WWP

Base Part 

Number

1

SIN

Thread Size

Nominal K-Factor

Overall Length

Listings and Approvals

(Refer also to Design Criteria)

NPT

BSP

U.S.

metric

2

Inches

mm

cULus

4

LPCB

19391

VK310

1/2”

15 mm

5.6

80.6

2-3/16

56

A1

A1

B1

7

B1

8

NOTICE - Product Below - Limited Availability (Contact Local Viking Office)

06766B

VK310

1/2”

15 mm

5.6

80.6

2-3/16

56

A1

A1

B1

7

B1

8

Approved Temperature Ratings

A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C)

B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C)

Approved Finishes

1 - Brass, Chrome, White Polyester

5,6

, and Black 

Polyester

5,6

Footnotes

1

 Base part number is shown. For complete part number, refer to Viking’s current price schedule.

2

 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

3

 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.

4

 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.

5

 cULus Listed as corrosion resistant.

6

 Other colors are available on request with the same Listings and Approvals as the standard colors.

7

 CE Certified, Standard EN 12259-1, EC-certificate of constancy of performance 0832-CPR-S0021.

8

 MED Certified, Standard EN 12259-1, EC-certificate 0832-MED-1003.

DESIGN CRITERIA - UL

 

(Also refer to Approval Chart 1)

cULus Listing Requirements:

 

Microfast

®

 Quick Response Conventional Sprinkler VK310 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest 

edition of NFPA 13 for old style (conventional) sprinklers.

• 

Designed for use in Light and Ordinary Hazard occupancies

.

 

• 

The sprinkler installation rules contained in NFPA 13 for standard spray old style (conventional) sprinklers must be followed.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 

for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest 

edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and 

also with the provisions of governmental codes, ordinances, and standards, whenever applicable. 

Replaces Form No. F_022514 Rev 18.1

(Added P65 Warning.)

Содержание MICROFAST VK310

Страница 1: ...31 870 Thread size 1 2 15 mm NPT Nominal K Factor 5 6 U S 80 6 metric Glass bulb fluid temperature rated to 65 F 55 C Overall Length 2 3 16 56 mm cULus Listing and NFPA 13 installs require a minimum of 7 psi 0 5 bar The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi 0 35 bar Metric K factor measurment shown is in Bar When pressure is measured in kPa divide the metric K factor s...

Страница 2: ...schedule or contact Viking directly TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Bulb Color Ordinary 135 F 57 C 100 F 38 C Orange Ordinary 155 F 68 C 100 F 38 C Red Intermediate 175 F 79 C 150 F 65 C Yellow Intermediate 200 F 93 C 150 F 65 C Green High 286 F 141 C 225 F 1...

Страница 3: ...or shown by 10 0 3 This table shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals 4 Listed by Underwriters Laboratories Inc for use in the U S and Canada 5 cULus Listed as corrosion resistant 6 Other colors are available on request with the same Listings and Approvals as the standard colors 7 CE Certified Standard EN 12259 1 E...

Страница 4: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 5: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 6: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 7: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 8: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: