MICROFAST

®

 QUICK 

RESPONSE CONVENTIONAL 

SPRINKLER VK310 (K5.6)

TECHNICAL DATA

Page 1 of 3

Form No. F_022514    18.11.05    Rev 18.1.P65

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

1.  DESCRIPTION

The Viking Microfast

®

 Quick Response Conventional Sprinkler VK310 is a small, thermosensi-

tive, glass-bulb spray sprinkler available in several different finishes, temperature ratings, and 

K-factors to meet design requirements. The special Polyester coatings can be used in decorative 

applications where colors are desired. In addition, these coatings have been investigated for instal-

lation in corrosive atmospheres and are listed as corrosion resistant as indicated in the Approval 

Charts. 

2.  LISTINGS AND APPROVALS

cULus Listed:

 Category VNIV

LPCB Approved: 

Certificate 096e/04 

CE Certified:

 Standard EN 12259-1, EC-Certificate of constancy of performance 0832-

CPR-S0021

MED Certified:

 Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003

NOTE: 

Other International approval certificates are available upon request.

Refer to Approval Chart 1 and Design Criteria for cULus Listing requirements.

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar)* 

Maximum Working Pressure: 175 psi (12 bar)

 

Factory tested hydrostatically to 500 psi (34.5 bar)

Testing: U.S.A. Patent No. 4,831,870

Thread size: 1/2” (15 mm) NPT

Nominal K-Factor: 5.6 U.S. (80.6 metric**)

 

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

Overall Length: 2-3/16” (56 mm)

 *cULus Listing, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 

5 psi (0.35 bar).

** Metric K-factor measurment shown is in Bar.  When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 

Material Standards:

Frame Casting: Brass UNS-C84400 or QM Brass

Deflector: Brass UNS-C26000

Bulb: Glass, nominal 3 mm diameter

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Screw: Brass UNS-C36000

Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400

For Polyester Coated Sprinklers:

 

Belleville Spring-Exposed

Ordering Information:

 (Also refer to the current Viking price list.)

Order Microfast

®

 Quick Response Conventional Sprinkler VK310 by first adding the appropriate suffix for the sprinkler finish and 

then the appropriate suffix for the temperature rating to the sprinkler base part number. 

Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, and Black Polyester = M-/B

Temperature Suffix (°F/°C): 135°/57° = A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G

For example, sprinkler VK310 with a 1/2” thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 19391AB

Available Finishes And Temperature Ratings: 

Refer to Table 1.

Accessories:

 (Also refer to the Viking website.)

Sprinkler Wrench: 

Standard Wrench: Part No. 10896W/B (available since 2000)

 

Sprinkler Cabinets:

A. Six-head capacity: Part No. 01724A (available since 1971)

B. Twelve-head capacity: Part No. 01725A (available since 1971)

Replaces Form No. F_022514 Rev 18.1

(Added P65 Warning.)

Содержание MICROFAST VK310

Страница 1: ...31 870 Thread size 1 2 15 mm NPT Nominal K Factor 5 6 U S 80 6 metric Glass bulb fluid temperature rated to 65 F 55 C Overall Length 2 3 16 56 mm cULus Listing and NFPA 13 installs require a minimum of 7 psi 0 5 bar The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi 0 35 bar Metric K factor measurment shown is in Bar When pressure is measured in kPa divide the metric K factor s...

Страница 2: ...schedule or contact Viking directly TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Bulb Color Ordinary 135 F 57 C 100 F 38 C Orange Ordinary 155 F 68 C 100 F 38 C Red Intermediate 175 F 79 C 150 F 65 C Yellow Intermediate 200 F 93 C 150 F 65 C Green High 286 F 141 C 225 F 1...

Страница 3: ...or shown by 10 0 3 This table shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals 4 Listed by Underwriters Laboratories Inc for use in the U S and Canada 5 cULus Listed as corrosion resistant 6 Other colors are available on request with the same Listings and Approvals as the standard colors 7 CE Certified Standard EN 12259 1 E...

Страница 4: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 5: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 6: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 7: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 8: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: