INSTITUTIONAL SPRINKLERS K5.6

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Page 9 of 9

Form No. F_032319    20.01.03     Rev 20.1

© 2020 Viking Group Inc. All rights reserved

DESIGN CRITERIA - UL

STANDARD COVERAGE PENDENT

cULus Listing Requirements:

The sprinkler VK426 is cULus Listed as a Quick Response, Flush, Pendent Sprinkler as indicated in the Approval Chart for installation in accordance 

with the latest edition of NFPA 13. The following requirements must be followed:

• 

Designed for use in Light and Ordinary Hazard occupancies.

• 

The sprinkler must be installed in the pendent position in fixed fire protection systems (wet, dry, deluge, or preaction systems).

• 

Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. 

• 

Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13.

• 

Minimum distance from walls is 4 in. (100 mm).

• 

Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpen-

dicular to the wall.

• 

The sprinkler installation and obstruction rules contained in NFPA 13 for standard coverage spray pendent sprinklers must be followed.

EXTENDED COVERAGE PENDENT

cULus Listing Requirements:

The sprinkler VK650 is cULus Listed as an Extended Coverage, Quick Response, Flush, Pendent Sprinkler as indicated in the Approval Chart for 

installation in accordance with the latest edition of NFPA 13. The following requirements must be followed: 

• 

Designed for use in Light Hazard occupancies only.

• 

The sprinkler must be installed in the pendent position in fixed fire protection systems (wet, dry, deluge, or preaction systems).

• 

Minimum distance from walls is 4 in. (100 mm).

• 

Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpen-

dicular to the wall.

• 

The sprinkler installation and obstruction rules contained in NFPA 13 for extended coverage pendent spray sprinklers must be followed.

STANDARD COVERAGE HORIZONTAL SIDEWALL

cULus Listing Requirements:

The sprinkler VK427 is cULus Listed as a Quick Response, Flush, Horizontal Sidewall Sprinkler as indicated in the Approval Chart for installation in 

accordance with the latest edition of NFPA 13. The following requirements must be followed:

• 

Designed for use in Light and Ordinary Hazard occupancies below smooth, flat, horizontal ceilings.

• 

The sprinkler must be installed in the horizontal sidewall position in fixed fire protection systems (wet, dry, deluge, or preaction systems).

• 

Orient the top of the deflector parallel with the ceiling. The wrench ear on the top of the Viking Institutional Style Quick Response Flush Horizontal 

Sidewall Sprinkler is marked with the word “top”.

• 

Must be located with deflector 4” to 12” (102 mm to 304 mm) below the ceiling, and flush with the wall in which they are installed.

• 

Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. 

• 

Minimum spacing allowed is 6 ft. (1.8 m).

• 

Minimum distance from end walls is 4 in. (102 mm).

• 

Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured 

perpendicular to the wall.

• 

The sprinkler installation and obstruction rules contained in NFPA 13 for standard coverage spray horizontal sidewall sprinklers must be followed.

EXTENDED COVERAGE HORIZONTAL SIDEWALL

cULus Listing Requirements:

The sprinkler VK651 is cULus Listed as an Extended Coverage, Quick Response, Flush, Horizontal Sidewall Sprinkler as indicated in the Approval 

Chart for installation in accordance with the latest edition of NFPA 13. The following requirements must be followed: 

• 

Designed for use in Light Hazard occupancies only below smooth, flat, horizontal ceilings.

• 

The sprinkler must be installed in the horizontal sidewall position in fixed fire protection systems (wet, dry, deluge, or preaction systems).

• 

Orient the top of the deflector parallel with the ceiling. The wrench ear on the top of the Viking Institutional Style Quick Response Flush Horizontal 

Sidewall Sprinkler is marked with the word “top”.

• 

Must be located with deflector 4” to 12” (102 mm to 304 mm) below the ceiling, and flush with the wall in which they are installed.

• 

Maximum Protection area allowed is  16’ x 16’ (4.9 m x 4.9 m) 

• 

Maximum spacing shall be in accordance with the tables provided in NFPA 13. 

• 

Minimum spacing allowed is 6 ft. (1.8 m).

• 

Minimum distance from end walls is 4 in. (102 mm).

• 

Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured 

perpendicular to the wall.

• 

The sprinkler installation and obstruction rules contained in NFPA 13 for standard coverage spray horizontal sidewall sprinklers must be followed. 

IMPORTANT: Always refer to Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for 

general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest 

edition of Viking Technical Data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and 

also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Replaces F_032319 Rev 19.2

(Replaced escutcheon PNs)

Содержание K5-6

Страница 1: ...erage Flush sprinklers for extended areas of coverage up to 16 x 16 4 9 m x 4 9 m in Light Hazard occupancies only below smooth flat horizontal ceilings Refer to the Approval Chart and Design Criteria for requirements that must be followed NOTICE THE VIKING CORPORATION DISCLAIMS ANY RESPONSIBILITY FOR DAMAGES OR INJURY INCLUDING DEATH CAUSED BY THE OPERATION OR INOPERATION OF SPRINKLERS ARISING OU...

Страница 2: ...96 QR EC HSW 22907 VK651 15 4 100 mm 23197 Examples Sprinkler 19663MC RAL9006 VK426 Quick Response Pendent with Painted gray Finish and 165 F 74 C Nominal tempera ture rating This sprinkler is to be installed into an area with a maximum ambient temperature of 100 F 38 C meaning if the area will experience temperatures above the maximum ambient rating you shall use a higher temperature rated sprink...

Страница 3: ...1 03 Rev 20 1 2020 Viking Group Inc All rights reserved Figure 3 Sprinkler Components and Identification Horizontal Sidewall Pendent Pendent Deflector Sprinkler Type indicator Sprinkler Type indicator Horizontal Sidewall Deflector Sprinkler Data Location Stamped around the permimeter you will find Sprinkler Identification Number SIN K factor Coverage No mark for Standard Coverage and EC for Extend...

Страница 4: ...orporation Flush sprinklers are decorative sprinklers and may be considered special purpose As such some Authorities may limit the use depending on the occupancy classification Refer to the Authority Having Jurisdiction prior to installation General Information The tamper resistant design of the Viking Institutional Sprinklers is dependant upon proper installation as outlined in this document as w...

Страница 5: ...king on the protective cap Place the sprinkler wrench over the protective cap on the sprinkler body NOTE The wrench is uniquely designed to fit over the sprinkler cap and into the sprinkler in a specific alignment 6 Install the sprinkler into the fitting NOTE The Escutcheon plate MUST be tight against the ceiling or wall 7 Tighten the sprinkler to approximately 7 14 ft lbs 8 If desired use a level...

Страница 6: ...sleeve 2 I D Cored Hole OR 2 Sch 40 Steel pipe sleeve Figure 5 Installation Dimensions Pendent Figure 6 Installation Dimensions HSW Upon activation the deflector actuates to approximately 7 8 22 mm beyond the sprinkler body 1 5 16 33 mm 1 4 6 mm 3 or 4 75 or 100 mm Face of fitting to finished surface of wall 7 8 22 mm Ensure the escutcheon plate is tight against the ceiling Ensure the escutcheon p...

Страница 7: ... and or replaced immediately as required Installation standards require sprinklers to be tested and if necessary replaced after a specified term of service Refer to the installation standards and the Authority Having Jurisdiction for the specified period of time after which testing and or replacement is required Sprinklers that have operated cannot be reassembled or reused but must be replaced Whe...

Страница 8: ...part number refer to Viking s current price schedule 2 This table shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals 3 Other colors are available upon request with the same Listings and Approvals as the standard colors LISTED FLOW RATES AND COVERAGE AREAS LIGHT HAZARD FOR Viking EXTENDED COVERAGE Institutional Sprinklers Spri...

Страница 9: ...nkler must be installed in the horizontal sidewall position in fixed fire protection systems wet dry deluge or preaction systems Orient the top of the deflector parallel with the ceiling The wrench ear on the top of the Viking Institutional Style Quick Response Flush Horizontal Sidewall Sprinkler is marked with the word top Must be located with deflector 4 to 12 102 mm to 304 mm below the ceiling ...

Отзывы: