VK1181 STANDARD 

RESPONSE CONVENTIONAL 

SPRINKLER (K5.6)

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Page 3 of 4

Form No. F_102518    Rev 22.1     March 3, 2022

DESIGN CRITERIA - UL

cULus Listing Requirements:

The Viking Standard Response Conventional Sprinkler VK1181 is cULus Listed as indicated in the Approval Chart for installation in 

accordance with the latest edition of NFPA 13 for old style (conventional) sprinklers.

•  Designed for use in Light, Ordinary, and Extra Hazard occupancies.

•  The sprinkler installation rules contained in NFPA 13 for standard spray old style (conventional) sprinklers must be followed.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 

for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest 

edition of Viking technical data, the appropriate standards of NFPA, LPCB, or other similar organizations, and also with the 

provisions of governmental codes, ordinances, and standards, whenever applicable.

APPROVAL CHART

Standard Response Conventional Sprinkler 

VK1181 K5.6 (80.6 metric)

Maximum 175 PSI (12 bar) WWP

Sprinkler Base 

Part Number

1

Thread Size

Listings and Approvals

2

NPT BSPT

cULus

LPCB

5

Inch

mm

Approval Specification

Approval Specification

22100

1/2

--

A1

A1

22106

--

15

A1

A1

Approved Temperature Ratings

A

 = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C) and 286 °F (141 °C)

Approved Finishes

1

 = Brass, Chrome, White Polyester 

3,4

, Black Polyester 

3,4

, and ENT

 4

Footnotes

Base Part number is shown. For complete part number, refer to Viking’s current price schedule.

This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.

Other colors are available upon request with the same Listings and Approvals as the standard colors.

cULus Listed as corrosion resistant.

LPCB approved; reference no. 096m 

Содержание 23907

Страница 1: ...bulb fluid temperature rated to 65 F 55 C Metric K factor measurement shown is when pressure is measured in Bar When pressure is measured in kPa divide the metric K factor shown by 10 0 Material Stan...

Страница 2: ...ill experience temperatures above the maximum ambient rating you shall use a higher temperature rated sprinkler Accessories Sprinkler Wrenches see Figure 1 A Installer Wrench Part No 22055 available s...

Страница 3: ...stallation and maintenance information Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data the appropriate standards of NFPA LPCB or other similar orga...

Страница 4: ...r the latest edition of this technical data page www vikinggroupinc com Page 4 of 4 Form No F_102518 Rev 22 1 March 3 2022 Frame arms parallel to the pipe 1 2 3 1 Slide the wrench around the protectiv...

Страница 5: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Страница 6: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Страница 7: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Страница 8: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Страница 9: ...readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification...

Страница 10: ...y intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler...

Страница 11: ...ENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking C...

Страница 12: ...e sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any s...

Страница 13: ...ctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements...

Страница 14: ...her To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVI...

Страница 15: ...rior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service d...

Страница 16: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Страница 17: ...render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation Refer to the Authority Having Jurisdiction prior to installation 2 GENERA...

Отзывы: