MICROMATIC
®
STANDARD
RESPONSE HORIZONTAL
SIDEWALL SPRINKLER
VK104 (K5.6)
TECHNICAL DATA
Page 4 of 6
Form No. F_033514 19.11.18 Rev 19.4
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1 above.)
cULus Listing Requirements:
The Micromatic
®
Viking Standard Response Horizontal Sidewall Sprinkler VK104 is cULus Listed as indicated in the Approval Chart for installation in accordance with
the latest edition of NFPA 13 for sidewall standard spray sprinklers.
•
For use in Light Hazard occupancies only where allowed by the installation standards being applied.
•
Locate the deflector 4” to 12“ (102 mm to 305 mm) below the ceiling.
•
Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13.
•
Minimum spacing allowed is 6 ft. (1.8 m).
•
Align the top of the deflector parallel with the ceiling.
•
Locate no less than 4” (102 mm) from end walls.
•
Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall.
•
The sprinkler installation and obstruction rules contained in NFPA 13 for sidewall standard spray sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Bulletin Form No. F_080614 for
general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking
technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of gov-
ernmental codes, ordinances, and standards, whenever applicable.
Approval Chart 1 (UL)
Micromatic
®
Viking Standard Response Horizontal Sidewall Sprinkler VK104
For Light Hazard Occupancies Only
Maximum 175 PSI (12 Bar) WWP
Sprinkler
Base Part
Number
1
SIN
Thread Size Nominal K-factor Overall Length
Listings and Approvals
3
(Refer also to UL Design Criteria.)
NPT BSPT U.S.
metric
2
Inches mm
cULus
4
LPCB
MED
CE
8
China
Approval
12995
VK104 1/2”
--
5.6
80.6
2-1/2”
64
A1Z, B1X, B2X, C4Z, E4Y
A1Z, B2Z
C1
9
C1Z
8
--
12988
VK104
-- 15 mm 5.6
80.6
2-1/2”
64
A1Z, B1X, B2X, C4Z, E4Y
A1Z, B2Z
C1
9
C1Z
8
--
20230
10
VK104
-- 15 mm 5.6
80.6
2-1/2”
64
D3
--
--
--
D3
NOTICE - Product Below - No longer offered.
10224
VK104 1/2”
--
5.6
80.6
2-1/2”
64
B2W, B1W, A1X
A1Z
C1
9
C1Y
8
C1Z
9
10171
VK104
-- 15 mm 5.6
80.6
2-1/2”
64
B2W, B1W, A1X
A1Z
C1
9
C1Y
8
C1Z
9
Approved Temperature Rating Codes
A = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C), and 360 °F (182 °C)
B = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
C = 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C), and 360 °F (182 °C)
D = 155 °F (68 °C)
E = 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
Approved Finish Codes
1 = Brass, Chrome, White Polyester
6,7
, and Black Polyester
6,7
2 = Wax-Coated Brass and Wax Over Polyester (corrosion resistant)
3 = Chrome
4 = ENT
6
Approved Escutcheon Codes
W = Standard surface-mounted escutcheons or recessed with the Viking Model E-1, E-2, E-3, or Model G-1 Recessed Escutcheons
X = Standard surface-mounted escutcheons or recessed with the Viking Model E-1, E-2, or E-3 Recessed Escutcheons
Y = Installed with surface-mounted escutcheons or recessed with the Viking Model E-1 Recessed Escutcheons
Z = Installed with surface-mounted escutcheons only
Footnotes
1.
Base part number shown. For complete part number, refer to Viking’s current price schedule.
2.
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3.
This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
4.
Listings and Approvals are limited to Light Hazard Occupancies where allowed by the installation standards being applied.
5.
Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
6.
cULus Listed as corrosion-resistant.
7.
Other colors are available on request with the same Listings and Approvals as the standard colors.
8.
Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-0021 and 0832-CPD-2003.
9.
MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008.
10.
Approved according to China GB standard.