Viking 06932B Скачать руководство пользователя страница 1

MICROFAST

®

 

QUICK RESPONSE 

PENDENT SPRINKLER 

VK3311 (K4.2)

TECHNICAL DATA

Page 1 of 5

Form No. F_061914    19.02.21    Rev 19.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

1.  DESCRIPTION

The Viking Microfast

®

 Quick Response Pendent Sprinkler VK3311 is a small 

thermosensitive glass bulb spray sprinkler available with various finishes and 

temperature ratings to meet design requirements. The special Polyester and PTFE 

coatings can be used in decorative applications where colors are desired. In ad-

dition, these coatings have been investigated for installation in corrosive atmos-

pheres and are listed/approved as corrosion resistant as indicated in the Approval 

Charts.

2.  LISTINGS AND APPROVALS

VdS Approved:

 Certificates G4040095, G4040097, G4060056, G4060057, 

G4880045, G4930038, and G4980021

CE Certified:

 Standard EN 12259-1, EC-certificates of conformity 

0786-CPD-40130, 0786-CPD-40170

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar) 

Rated to 175 psi (12 bar) water working pressure

Factory tested hydrostatically to 500 psi (34.5 bar)

Thread size: 10 mm BSP

Nominal K-Factor: 4.2 U.S. (57 metric**)

 

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

Overall Length: 2-1/4” (58 mm)

Material Standards:

Frame Casting: Brass UNS-C84400 

Deflector: Brass UNS-C26000

Bushing: Brass UNS-C36000

Bulb: Glass, nominal 3 mm diameter

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Screw: Brass UNS-C36000

Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400

For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated 

For Polyester Coated Sprinklers:

 

Belleville Spring-Exposed

Ordering Information:

 (Also refer to the current Viking price list.)

Order Viking Microfast

®

 Quick Response Pendent Sprinkler VK3311 by first adding the appropriate suffix for the sprinkler finish and 

then the appropriate suffix for the temperature rating to the sprinkler base part number. 

Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and Black PTFE = N

Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G

For example, sprinkler VK3311 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 06932BAB

Available Finishes And Temperature Ratings:

 Refer to Table 1.

Accessories:

 (Also refer to the Viking website.)

Sprinkler Wrenches:

A. Standard Wrench: Part No. 21475M/B (available since 2017). 

B. Wrench for Recessed Pendent Sprinklers: Part No. 13655W/B** (available since 2006)

C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010)

  **A ½” ratchet is required (not available from Viking).

     ***Allows use from the floor by attaching a length of 1” diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808.

Replaces form F_061914 Rev. 17.2.P65

(Removed F-1 Escutcheon.)

Содержание 06932B

Страница 1: ...Casting Brass UNS C84400 Deflector Brass UNS C26000 Bushing Brass UNS C36000 Bulb Glass nominal 3 mm diameter Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Screw...

Страница 2: ...s the heat sensitive liquid in the glass bulb expands causing the glass to shatter releasing the pip cap and sealing spring assembly Water flowing through the sprinkler orifice strikes the sprinkler d...

Страница 3: ...Polyester and Black PTFE Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requi...

Страница 4: ...te Polyester4 and Black Polyester4 2 Brass and Chrome Footnotes 1 Base part number shown For complete part number refer to Viking s current price schedule 2 Metric K factor measurement shown is when p...

Страница 5: ...igure 4 Sprinkler Dimensions with the Model E 1 and E 2 Recessed Escutcheons Figure 3 Sprinkler Dimensions with a Standard Escutcheon 1 2 10 mm NPT 2 1 4 57 mm Installed with a standard 1 8 surface mo...

Страница 6: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Страница 7: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Страница 8: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Страница 9: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Страница 10: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Отзывы: