Document: LT0109
Vigilant MICROVAC Owner's Manual
Operation
Issue 1.31
5 April 2000
Page 3-3
Strobe Fault
Indicates a fault in the strobe wiring.
Silence
Indicates any of the above fault or alarm conditions.
Beeper
Indicates a fault or alarm which is still present and has not been acknowledged.
3.3 STATUS
INDICATORS
EVACUATE
Indicates an automatic or manually-generated activation of the Evacuate signal.
ALERT
Indicates an automatic or manually-generated activation of the Alert signal.
PA
Indicates that the PA (Speech) function has been manually activated. (Note the PTT
button on the microphone will need to be pressed before the microphone is
activated.)
MAINS ON
Indicates that Mains power is available. Note that this indicator is derived directly
from incoming mains and is not affected by the LAMP TEST function.
AUTO
Indicates that the keyswitch is in the AUTO position, and in networked mode also
indicates that no other ECP in the system has manual or isolate control.
MANUAL
When steady indicates that the keyswitch is in the MANUAL position and manual
control is available. In networked mode, will flash with a flash-flash-pause cadence
to indicate that another ECP has manual control.
ISOLATE
When steady indicates that the keyswitch is in the ISOLATE position and all outputs
are disabled. In networked mode, will flash with a flash-flash-pause cadence to
indicate that another ECP has isolated the zone and all outputs are disabled.
Содержание MICROVAC
Страница 34: ......