3
4.3 Load mode setting
Operating Steps:
Under load mode setting interface, press SET button and hold on 5s
begin flashing, then press MENU button to set the parameter, press
confirm.
1**
Timer 1
2**
100
Light ON/OFF
2 n
Disable
101
Load will be on for 1 hour
since sunset
201
Load will be on for 1 hour
before sunrise
102
Load will be on for 2 hours
since sunset
202
Load will be on for 2 hour
before sunrise
103
~
113
Load will be on for 3
~
13
hours since sunset
203
~
213
Load will be on for
hour
114
Load will be on for 14 hours
since sunset
214
Load will
hour
115
Load will be on for 15 hours
since sunset
215
Load will be on for 15
hour
116
Test mode
2 n
Disabled
117
Manual mode(Default load
ON)
2 n
Disabled
NOTE: Please set Light ON/OFF, Test mode and Manual mode via Timer1.
will be disabled and display "2 n".
4.4 Battery Type
Operating Steps
Under Battery Voltage interface, press SET button and hold on 5s
interface of Battery type setting. After choosing the battery type by pressing
button, waiting for 5s or pressing SET button again to modify successfully.
Battery Type
①
Sealed (Default)
②
Gel
③
NOTE: Please refer to the battery voltage parameters table
battery type.
5. Protections
PV Short Circuit
When PV short circuit occurs, the controller will stop charging. Clear it to resume normal
operation.
PV Reverse Polarity
Fully protection against PV reverse polarity, correct the wire connection to resume
normal operation.
Battery Reverse Polarity
Fully protection against battery reverse polarity, correct the wire connection to resume
normal operation.
Warning
:
Shock Hazard!
When the battery is reverse, the load will appear the equal
polarity voltage to battery.
Battery Over Voltage
When the battery voltage reaches to the set point of Over Voltage
the controller will stop charging the battery to protect the battery from being over
charged to break down.
Battery Over Discharge
When the battery voltage reaches to the set point of Low Voltage Disconnect
the controller will stop discharging the battery to protect the battery from being ove
discharged.
Battery Overheating
The controller detect the battery temperature through the external temperature sensor. If
the battery temperature exceeds 65ºC, the controller will automatically start the
overheating protection to stop working and recover below 50 ºC.
Load Overload
Load will be switched off when 1.05 times rated current overload happens. Controller
will automatically attempt to reconnect load for 5 times. If overload protection still exist
after controller’s 5 times attempts, user have to reduce load appliance, then
SET button or repower the controller or wait for one night-day cycle (night time>3
hours).
Load Short Circuit
Load will be switched off when load short circuit (
≥
4 times rated current) happens.
Controller will automatically attempt to reconnect load for 5 times. If short circuit
protection still exist after controller’s 5 times attempts, user have to
circuit ,then press the SET button or disconnect and restart the controller or wait for one
night-day cycle (night time>3 hours).
Damaged Remote Temperature Sensor
If the temperature sensor is short-circuited or damaged, the controller will be charging or
discharging at the default temperature 25 to preven
℃
t the battery damaged from
overcharging or over discharged.
Controller Overheating
If the temperature of the controller heat sinks exceeds 85 , the co
℃
automatically start the overheating protection and recover below 75
High Voltage Transients
PV is protected against small high voltage surge. In lightning prone areas, additional
external suppression is recommended.
and hold on 5s till the number
to set the parameter, press SET button to
Timer 2
Disabled
Load will be on for 1 hour
before sunrise
Load will be on for 2 hours
before sunrise
Load will be on for 3
~
13
hours before sunrise
Load will be on for 14
hours before sunrise
Load will be on for 15
hours before sunrise
Disabled
Disabled
Please set Light ON/OFF, Test mode and Manual mode via Timer1. Timer2
and hold on 5s then enter into the
interface of Battery type setting. After choosing the battery type by pressing MENU
button again to modify successfully.
Flooded
NOTE: Please refer to the battery voltage parameters table for the different
When PV short circuit occurs, the controller will stop charging. Clear it to resume normal
orrect the wire connection to resume
orrect the wire connection to resume
ear the equal and reverse
When the battery voltage reaches to the set point of Over Voltage Disconnect Voltage,
charging the battery to protect the battery from being over
When the battery voltage reaches to the set point of Low Voltage Disconnect Voltage,
battery from being over
The controller detect the battery temperature through the external temperature sensor. If
the battery temperature exceeds 65ºC, the controller will automatically start the
Load will be switched off when 1.05 times rated current overload happens. Controller
ill automatically attempt to reconnect load for 5 times. If overload protection still exist
reduce load appliance, then press the
day cycle (night time>3
4 times rated current) happens.
Controller will automatically attempt to reconnect load for 5 times. If short circuit
protection still exist after controller’s 5 times attempts, user have to clear short
controller or wait for one
circuited or damaged, the controller will be charging or
t the battery damaged from
controller will
℃
automatically start the overheating protection and recover below 75 .
℃
PV is protected against small high voltage surge. In lightning prone areas, additional
6. Troubleshooting
Faults
Possible reasons
The
LCD
is
off
during daytime when
sunshine falls on PV
modules properly
PV
array
disconnection
Wire connection is
correct,
LCD
not
display
1. Battery voltage is
lower than 9V
2. PV voltage is less
than battery voltage
Interface
blink
Battery over voltage
Interface
blink
Battery
over discharged
Interface
blink
Battery Overheating
Interface
blink
Over load or
circuit
7. Technical Specifications
Item
VS1024A
Nominal system voltage
Battery input voltage
range
Rated charge current
10A
Max. PV open circuit
voltage
Temperature
compensation coefficient
Self-consumption
Charge circuit voltage drop
Discharge circuit voltage
drop
LCD temperature range
Working environment
temperature
Humidity range
Enclosure
Grounding
Overall dimension
132x84.6
x39.7mm
Mounting dimension
120x56mm
Mounting hole size
Terminals
4mm
2
Net weight
0.18kg
* If the controller is working under high temperature environment,
capacity in service
Battery Voltage Parameters (parameters is in 12V system at 25
value in 24V.)
Battery charging setting
Over Voltage Disconnect Voltage
Charging Limit Voltage
Over Voltage Reconnect Voltage
Equalize Charging Voltage
Boost Charging Voltage
Float Charging Voltage
Boost Reconnect Charging Voltage
Low Voltage Reconnect Voltage
Under Voltage Warning Reconnect Voltage
Under Volt. Warning Volt.
Low Volt. Disconnect Volt.
Discharging Limit Voltage
Equalize Duration
Boost Duration
8. Disclaimer
1) Damage from improper use or use in an
2)
PV or load current, voltage or power exceeding the rated value of controller.
3) User disassembly or attempted repair the controller without permission.
4) The controller is damaged due to natural elements such as lighting.
5)
The controller is damaged during transportation and shipment.
Any changes without prior notice!
4
Possible reasons
Troubleshooting
PV
array
disconnection
Confirm that PV wire connections
are correct and tight
1. Battery voltage is
lower than 9V
2. PV voltage is less
voltage
1. Please check the voltage of
battery. At least 9V voltage to
activate the controller
2. Check the PV input voltage
which should be higher than
battery’s
Battery over voltage
Check if the battery voltage is
higher than OVD point (over
voltage disconnect voltage), and
disconnect the PV.
over discharged
When the battery voltage is
restored to or above LVR point
(low voltage reconnect voltage),
the load will recover
Overheating
The controller will automatically
turn the system off. But while the
temperature decline to be below
50 ºC, the controller will resume.
Over load or Short
Please reduce the number of
electric equipments or check
carefully loads connection.
VS1024A
VS2024A
VS3024A
12/24VDC Auto
9
~
32V
20A
30A
50V
-3mV/
℃
/2V
(
25
℃)
≤
8.1mA(12V);
≤
6.5mA(24V)
≤
0.29V
≤
0.16V
-20
℃~
+55
℃
-25
℃~
+55
℃*
≤
95% (N.C.)
IP30
Common Positive
132x84.6
x39.7mm
149x94.1
x46.1mm
177.5x106.6
x46.2mm
120x56mm
137x60mm
165.5x70mm
Φ
4.5mm
2
10mm
2
16mm
2
0.18kg
0.26kg
0.33kg
is working under high temperature environment, please derate
(parameters is in 12V system at 25
℃
, please use double
Sealed
Gel
Flooded
16.0V
16.0V
16.0V
15.0V
15.0V
15.0V
15.0V
15.0V
15.0V
14.6V
——
14.8V
14.4V
14.2V
14.6V
13.8V
13.8V
13.8V
13.2V
13.2V
13.2V
12.6V
12.6V
12.6V
Under Voltage Warning Reconnect Voltage
12.2V
12.2V
12.2V
12.0V
12.0V
12.0V
11.1V
11.1V
11.1V
10.6V
10.6V
10.6V
120min
——
120min
120min
120min
120min
Damage from improper use or use in an unsuitable environment.
PV or load current, voltage or power exceeding the rated value of controller.
User disassembly or attempted repair the controller without permission.
The controller is damaged due to natural elements such as lighting.
The controller is damaged during transportation and shipment.
Any changes without prior notice!
Version number
:
V1.0