Power supply independent of the mains isolator
Effects during heating system shutdown:
■
The control unit is switched off.
■
The gateway remains in operation.
■
No data is transferred to the KNX/EIB control sys-
tem.
Danger
Incorrect core assignment can result in serious
injury and damage to the appliance.
Take care not to interchange cores "L1" and "N":
L1 Brown (BN)
N
Blue (BU)
PE Green/yellow (GNYE)
B
C
E
F
L
PE
N
BN
BU
GNYE
H
A
+
-
G
D
K
Fig. 17
A
Gateway
B
Power supply 100 to 230 V~, 50 to 60 Hz
C
Fuse protection across all poles (max. 16 A)
D
Junction box (on site)
E
Mains isolator, 2-pole, on site (if installed)
F
Control unit power supply (plug
fÖ
)
G
Power supply unit
H
Earthing of top-hat rail to ensure that the shielding
of the CAN bus cable is earthed/protects against
interference.
K
Cores supplied
Installation sequence
Power supply
(cont.)
5853847
Installation
Содержание WAGO KNX/TP gateway
Страница 20: ...20 PE N L SYS 0V RST RUN l 0 MS NS USR 24V Fig 15 Installation sequence Power supply cont 5853847 Installation...
Страница 25: ...25 Dismounting the KNX terminal 1 2 4 3 Fig 19 Dismounting the gateway cont 5853847 Service...
Страница 26: ...26 Dismounting the CAN terminal 2 1 Fig 20 Dismounting the gateway cont 5853847 Service...
Страница 27: ...27 Dismounting the controller 1 3 2 Fig 21 Dismounting the gateway cont 5853847 Service...
Страница 28: ...28 1 2 Fig 22 Dismounting the power supply unit 5853847 Service...
Страница 34: ...34 5853847...
Страница 35: ...35 5853847...