Страница 1: ...tions Vitotronic 300 Model KW3 Weather responsive indoor outdoor digital boiler control for heating systems with one or more heating circuits Part No Z001 231 Certified as a component part of Viessman...

Страница 2: ...rtant Regulatory and Installation Requirements Advice to owner Once the installation work is complete the heating contractor must familiarize the system operator ultimate owner with all equipment as w...

Страница 3: ...m with two heating circuits with mixing valves 7 Application Example 5 System with one direct connected heating circuit without mixing valve and two heating circuits with mixing valves 8 Electrical Co...

Страница 4: ...tank temperature sensor KM BUS participants Extension for two stage modulating burner 1 Heating circuit pump Boiler circuit DHW production pump accessory DHW recirculation pump field supplied where r...

Страница 5: ...recirculation pump installed on site Power supply 120 VAC 60 Hz Burner single stage 4 Burner two stage modulating 4 Required Equipment Description Qty Part No Vitotronic 300 1 Z001 231 Mixing valve ac...

Страница 6: ...cuit pump 2 DHW production pump accessory DHW recirculation pump field supplied where required Power supply 120 VAC 60 Hz Burner single stage 4 Burner two stage modulating 4 Required Equipment Descrip...

Страница 7: ...rcuit pump 2 DHW production pump accessory DHW recirculation pump field supplied where required Power supply 120 VAC 60 Hz Burner single stage 4 Burner two stage modulating 4 Required Equipment Descri...

Страница 8: ...Mixing valve circuit pump 2 Heating circuit pump DHW production pump accessory DHW recirculation pump field supplied where required Power supply 120 VAC 60 Hz Burner single stage 4 Burner staging tak...

Страница 9: ...pump module Do not connect any external equipment directly Low voltage connectors Outdoor temperature sensor Boiler temperature sensor DHW tank temperature sensor 1 BDHW tank temperature sensor 2 Flu...

Страница 10: ...ating of 15 A L and N L LINE N Neutral G Ground This equipment must be grounded Ensure that the following wires are not interchanged WARNING 120 VAC 60 Hz 1 Ph Power supply Provide 15 A overcurrent pr...

Страница 11: ...ater cut off device typical 11 Vitotronic Connections continued Low water cut off connections 1 Run 3 conductor cable between low water cut off device and Power Pump Module 2 Remove jumper on Power Pu...

Страница 12: ...of strain relief clamp 3 Insert the cable in the bushing and secure the wires to the plug in connector Insert bushing in clamp and connector in socket 4 Fasten top portion of strain relief clamp No a...

Страница 13: ...ered wall allow room for plaster or remove sensor before plastering wall 1 Remove sensor housing 2 Secure wall mount base to wall cable inlet opening to the bottom 3 Pass cabling through openings in t...

Страница 14: ...rol unit Heating systems with domestic hot water heating 1 Install the DHW tank temperature sensor Installation Instructions for domestic hot water tank When installing the DHW tank temperature sensor...

Страница 15: ...or north western wall 2 to 2 5 m 6 5 to 8 ft above ground level in case of multi storey buildings in the upper half of the second floor Not above windows doors or ventilation outlets Not immediately...

Страница 16: ...r underfloor heating system only An adjustable high limit must be provided additionally Install the fixed high limit in the heating supply pipe downstream from the mixing valve and the heating circuit...

Страница 17: ...ter The Vitotronic 300 is prewired with the Viessmann quick connect plug in system 1 Connect the RAST 5 plug in connector to the main circuit board of the control 2 Connect 7 pole plug to the counter...

Страница 18: ...ol unit burner p Signal direction Burner control unit The connection is made via the extension for 2 stage modulating burner See Installation Instructions for boiler and extension for 2 stage modulati...

Страница 19: ...ly strain relief to the cable see Application of Strain Relief When the contact is closed the manually preselected program can be changed for all heating circuits at the same time See Vitotronic 300 S...

Страница 20: ...to the rear 4 Turn slotted screw on the rear of the fixed high limit and set to 212 F 100 C once adjusted the fixed high limit cannot be reset to 230 F 110 C 5 Put front panel cover and fuse back in...

Страница 21: ...ixed High Limit contd Adjustment to 100 C JUMO The fixed high limit is factory preset to 230 F 110 C 5303 269 v1 3 2 1 4 3 5 6 If adjusted to 212 F 100 C do not set the adjustable high limit above 167...

Страница 22: ...rn the selector knob fully clockwise 4 Check the box in the Vitotronic 300 Service Instructions to confirm that the adjustment was made If the system is operated in conjunction with a domestic hot wat...

Страница 23: ...e holding clip at the bottom of the control 5 Insert the flat cable connector in plug in location X10 and lay cable under holding clip 6 Unlock hinged support bar by applying pressure to linkage point...

Страница 24: ...ns regarding start up and settings Service document ring binder 1 File Installation Operating and Service Instructions in service binder 2 Service box optional equipment now available for service bind...

Страница 25: ...Appendix 25 5303 269 v1 3...

Страница 26: ...Appendix 26 5303 269 v1 3...

Страница 27: ...Appendix 27 5303 269 v1 3...

Страница 28: ...smann ca mail viessmann ca Viessmann Manufacturing Company U S Inc 45 Access Road Warwick Rhode Island 02886 USA Tel 401 732 0667 Fax 401 732 0590 www viessmann us com mail viessmann us com 28 Printed...