Modulating burner
Low temperature boiler
Vitocrossal
Function
External burner start
—
base load
Connection
Plug
aVD
.1/
aVD
.2
Plug
aVD
.1/
aVD
.2
143
A
B
2 3
1
A
Floating contact
B
To the control unit
143
A
B
2 3
1
A
Floating contact
B
To the control unit
Contact
■
Closed
■
The burner is started with base load.
■
An external modulation controller regu-
lates the load-dependent modulation.
■
The burner is switched to full load to
maintain the minimum temperature.
■
The boiler water temperature is restricted
by the electronic maximum temperature
limiter if this limiter is set below the level
of the mechanical temperature controller.
■
The burner is started with base load.
■
An external modulation controller regu-
lates the load-dependent modulation.
■
The boiler water temperature is restricted
by the electronic maximum temperature
limiter if this limiter is set below the level of
the mechanical temperature controller.
■
Open
The burner is switched OFF.
The burner is switched OFF.
Hooking up on-site control units via Vitogate
Set parameter "01:1" in the
"General"
group.
Note
For further information on hooking up on-site control
units via Vitogate, see
External functions — single boiler system
Connecting the external control unit
(cont.)
5863679
Installation