24
Pumps 400 V~
Rated current for switching the contactor: 4(2) A~
L
N
L1 L2 L3 N PE
A
C
3~
M
B
Fig. 14
A
Pump
B
To the control unit
C
Contactor
Connecting actuators
Connections on the 230 V~ PCB
Plug
Component
Single boiler system
Multi boiler system
gS
A1
One of the following functions:
■
Motorised butterfly valve
—
X
■
Mixing valve for return temperature con-
trol
X
X
■
Mixing valve, heat exchanger set
X
—
M
1~
52
Fig. 15
OPEN
CLOSE
Rated voltage
230 V~
Rated current
Max. 0.2 (0.1) A~
Runtime
5 to 199 s
Setting runtime
The runtime can be set by means of the following
parameters:
■
in conjunction with plug
gS
A1:
–
"56" in the
"General"
group
–
"0F" in the
"DHW"
group
Connecting a central fault message facility
Plug
gÖ
Faults from the respective boiler are transferred.
Electrical connections
Connecting pumps
(cont.)
5863679
Installation