19
7. Tap the
"Slope"
or
"Level"
buttons.
Temperature level diagram
Standard
values
Standard
mode
OK
°C
At an outside temp of ...
-30° -20° -10° 0° 10° 20°
70° 57° 48° 40° 30° 25°
+
-
1.0
0
Flow temperature curve setting
Slope
Level
Fig.22
8. Correct the values with the +/- buttons.
9. Press
"OK"
to confirm
■
You influence the heating characteristics by changing the slope or level of the heating curve.
Changing slope and level
Please use the following table as an aid to making adjustments:
Heating characteristics
Measures
Example
The living space is
too cold during the
heating season.
Set the heating curve
slope
to the
next
higher
value (e.g. 1.5).
Slope
1.5
Level
0 K
The living space is
too hot during the
heating season.
Set the heating curve
slope
to the
next
lower
value (e.g. 1.3).
Slope
1.3
Level
0 K
The living space is
too cold during spring/
autumn
and during the
heating season
.
Set the heating curve
level
to the
next
higher
value (e.g. +3).
Slope
1.4
Level
3 K
The living space is
too hot during spring/
autumn
and during the
heating season
.
Set the heating curve
level
to the
next
lower
value (e.g.
−
3).
Slope
1.4
Level
-3 K
The living space is
too cold during spring/
autumn
, but warm enough during the heat-
ing season.
Set the heating curve
slope
to the
next
lower
value and the
level
to a
higher
val-
ue.
Slope
1.3
Level
3 K
The living space is
too hot during spring/
autumn
, but warm enough during the heat-
ing season.
Set the heating curve
slope
to the
next
higher
value and the
level
to a
lower
val-
ue.
Slope
1.5
Level
-3 K
Note
Setting the heating curve slope or level too high or too low will not result in damage to your heating system.
For technically-minded system users
■
Heating curves illustrate the relationship between the outside temperature and the flow temperature. To put it
simply: The lower the outside temperature, the higher the flow temperature.
The illustrated heating curves apply with the following settings:
Central heating
Heating curve
(cont.)
5677 786 GB