DHW cylinder (if installed)
Standards DIN 1988-8 and EN 806 spec-
ify that maintenance and cleaning should
be carried out no later than 2 years after
commissioning and as required there-
after.
Only a qualified heating contractor
should clean the inside of a DHW cylin-
der and the DHW connections.
If any water treatment equipment (e.g. a
sluice or injection system) is installed in
the cold water supply of the DHW cylin-
der, ensure this is refilled in good time.
In this connection, observe the manufac-
turer's instructions.
In addition for Vitocell 100:
We recommend that the correct function
of the sacrificial anode is checked annu-
ally by your heating contractor.
The function of the sacrificial anode can
be checked without interrupting the sys-
tem operation. The heating contractor
will check the earth current with an
anode tester.
Safety valve (DHW cylinder)
The function of the safety valve must be
checked every six months by the user or
a contractor through venting (see valve
manufacturer's instructions). The valve
seat may become contaminated.
Water may drip from the safety valve
during a heat-up process. The outlet is
open to the atmosphere and must not be
closed off.
Potable water filter (if installed)
To maintain high hygienic standards,
proceed as follows:
■ Replace filter element on non-back
flushing filters every six months (visual
inspection every two months).
■ On back flushing filters, back flush
every two months.
Upkeep
Inspection and maintenance