22
■ For connecting the DHW side, observe
DIN 1988 and DIN 4753.
■ Connect all pipework with detachable
fittings.
■
Safety valve (accessory)
– Equip the system with a type-tested
safety valve as protection against
excessive pressure.
– Permissible operating pressure
6 bar.
– Install the safety valve in the cold
water line (see figure below).
– It must not be able to be isolated
from the DHW cylinder.
– The pipework between the safety
valve and the DHW cylinder must
not be restricted in any way.
– Never seal off the discharge pipe.
Expelled water should be safely and
visibly drained into a sewer. Place a
sign on the safety valve with the
inscription:
For safety reasons, water may be
discharged from the discharge
pipe during heating. Never seal
off.
A
B
N
C
E
G
D
F C
H
C K
C
H
G
L
M
A
Visible discharge pipe outlet
B
Safety valve
C
Shut-off valve
D
Flow regulating valve
E
Pressure gauge connector
F
Non-return valve
G
Drain
H
Cold water
K
Drinking water filter
L
Pressure reducer
M
Non-return valve/pipe separator
N
To the DHW cylinder
Information on the immersion heater (if installed)
We recommend installing an immersion
heater on site to protect the DHW cylin-
der against frost according to
DIN EN 60335-1 (VDE 0700-1) or
VDE 0700-253 and appropriate country-
specific standards.
Making the connections on the DHW side
5719 917 UAE
Содержание Vitosol 222-T
Страница 8: ...8 6 7 5 A B 7 9 4 A Foot support A B Foot support B Elevated installation cont 5719 917 UAE ...
Страница 10: ...10 1 6 0 0 4x 9 8 4x 10 3 1 6 Elevated installation cont 5719 917 UAE ...
Страница 13: ...13 1 4x 1 5 6 0 2 3 4x 4x Installation on pitched roofs cont 5719 917 UAE ...
Страница 14: ...14 5 6 4x 4x 4 4x 7 4x Installation on pitched roofs cont 5719 917 UAE ...
Страница 15: ...15 90 9 8x 8 2x Centre rail projections Installation on pitched roofs cont 5719 917 UAE ...
Страница 17: ...17 90 90 19 18 2x 4x 4 0 0 6 0 90 17 16 4x 2x Installation on pitched roofs cont 5719 917 UAE ...
Страница 18: ...18 90 21 2x 90 20 2x 1 5 9 7 Installation on pitched roofs cont 5719 917 UAE ...
Страница 19: ...19 22 23 4x Make the connections on the DHW side see page 22 Installation on pitched roofs cont 5719 917 UAE ...