24
Splitting the boiler block for easier transport into the boiler
room
(cont.)
Assembly of the boiler lying down
Note
Always use new nipples during assembly.
A
Clean the sealing faces (hub, grooves and tongues) with solvent
B
Fill the sealing grooves with sealant
C
Apply additional Dirko sealant in the marked area
D
Clean the nipples with solvent and apply the enclosed linseed oil graphite
5862915GB
B
A
D
C
2.
1.
3.