Viessmann Vitoplex 200 Series Скачать руководство пользователя страница 15

15

Partial load operation

Set the minimum heating output for the base load
stage in accordance with the flue system. The flue sys-
tem must be suitable for the low flue gas temperatures.

In the case of frequent cycling in standby mode and for
partial loads below 40 % we recommend that you:

Insulate the flue gas collector

Install a motorised flue gas damper

Set the minimum runtime of the boiler to 10 min

This extends the service life and reduces running
costs.

Operation with burner load 

 60 %

The minimum boiler water temperature for oil operation
is 50 °C and for gas operation 60 °C.
Adjust the return temperature raising facility to a mini-
mum of 40 °C (oil operation) or 53 °C (gas operation).
To protect the boiler, the minimum heating output in the
base load stage is set to 60 % of the rated output (see
table).

Rated heating out-
put

Minimum heating output to
be set (burner stage 1)

kW

kW

700

420

900

540

1100

660

1300

780

1600

960

1950

1170

The base load stage requires a minimum flue gas tem-
perature, the value of which is subject to the design of
the flue system.

Operation with burner load 

 40 % and < 60 %

The minimum system temperatures (flow/return) are
60/50 °C for oil operation and 70/60 °C for gas opera-
tion.

Operation with burner load < 40 %

The minimum system temperatures (flow/return) are
60/55 °C for oil operation and 70/65 °C for gas opera-
tion.

Instructing the system user

The installer should instruct the user in the operation of
the system.

Commissioning, inspection, maintenance

Adjusting the burner

 (cont.)

5692849

 

Содержание Vitoplex 200 Series

Страница 1: ...Service instructions for contractors VIESMANN Vitoplex 200 Type SX2A 700 to 1950 kW Oil gas boiler VITOPLEX 200 5692849 GB 9 2018 Please keep safe...

Страница 2: ...icable standards a NORM EN VGW G K directives VGW TRF and VE c SEV SUVA SVGW SVTI SWKI VKF and EKAS guideline 1942 LPG part 2 Safety instructions for working on the system Working on the system Where...

Страница 3: ...distribution board Danger If water escapes from the appliance there is a risk of scalding Never touch hot heating water Condensate Danger Contact with condensate can be harmful to health Never let co...

Страница 4: ...4 Parts list 26 4 Water quality Water quality requirements 28 Heating systems with rated operating temperatures up to 100 C VDI 2035 28 Prevention of damage through corrosion on the water side 29 Usin...

Страница 5: ...n Not required during inspection Steps required during maintenance Not required during maintenance Intended use The appliance is only intended to be installed and operated in sealed unvented heating s...

Страница 6: ...6 Vitoplex 200 type SX2A Fuels Fuel oil and natural gas Rated heating output 700 to 1950 kW Permiss operating pressure 6 bar 0 6 MPa Information Product information 5692849 Information...

Страница 7: ...he pressure switch 12 11 Checking the temperature controller setting if a building management system is used DCC system 12 12 Checking the expansion vessel and system pressure 12 13 Checking the firm...

Страница 8: ...ns 12 The dew point range must be cleared as quickly as possible For this reason prevent all heat sup ply to consumers when heating the system from cold This also applies when restarting after main te...

Страница 9: ...the boiler with a suction pump when the air vent valve is open Opening the boiler door and cleaning cover Note On gas burners disconnect the gas supply pipe 4x Fig 2 Cleaning the turbulators heating s...

Страница 10: ...cleaner Checking all gaskets and packing cords on the flue gas side Checking the thermal insulation components on the boiler door Danger Fibre dust can be produced if working with high temperature in...

Страница 11: ...ar into hot gas flues B Spring clip E must snap into place behind first constriction D Note This snapping into place prevents the turbulators from slipping forward during boiler operation 2 Tighten sc...

Страница 12: ...of the expansion vessel p0 is made up of the static system pressure pSt static head and a supplement p0 pSt sup plement The supplement depends on the high limit safety cut out setting The following a...

Страница 13: ...corrosion protection as described in VDI 2035 Part 2 Note Check the pressure maintaining system in line with the manufacturer s instructions Please note Cyclical pressure fluctuations and more signif...

Страница 14: ...he flue pipe for tightness Adjusting the burner Adjust the maximum oil or gas throughput of the burner to the rated boiler heating output Rated heating output Pressure drop on the hot gas side kW Pa m...

Страница 15: ...l operation or 53 C gas operation To protect the boiler the minimum heating output in the base load stage is set to 60 of the rated output see table Rated heating out put Minimum heating output to be...

Страница 16: ...tractor s section 2 File all parts lists operating and service instruc tions in the folder and hand this over to the system user The installation instructions are no longer required after the applianc...

Страница 17: ...Pos Part 229 Back panel retrofit kit matching pos 216 217 300 Thermal insulation small parts 301 Touch up spray paint Vitosilver 302 Touch up paint stick Vitosilver 303 Installation instructions 304...

Страница 18: ...18 For boiler sizes 700 to 1300 kW 011 010 012 008 009 001 024 025 004 005 006 007 003 308 Fig 6 Parts lists Parts list for boiler sizes 700 to 1300 kW 5692849 Components...

Страница 19: ...ss frame 005 Gasket 006 Hose nozzle 007 Plastic hose 008 Hose pack 18 mm 009 Upper insulation block 010 Lower insulation block 011 Thermal insulation mat 012 Pack GF 25 x 15 308 Logo 024 Burner plate...

Страница 20: ...20 For boiler sizes 1600 to 1950 kW 012 011 008 009 024 025 004 005 006 007 003 001 010 A 308 Fig 7 A Type plate Parts lists Parts list for boiler sizes 1600 to 1950 kW 5692849 Components...

Страница 21: ...05 Gasket 006 Hose nozzle 007 Plastic hose 008 Hose pack 18 mm 009 Upper insulation block 010 Lower insulation block 011 Thermal insulation mat 012 Pack GF 25 x 15 308 Logo 024 Burner plate 025 Gasket...

Страница 22: ...22 C 014 C 016 017 224 018 015 014 013 002 020 023 021 022 Fig 8 C Burner cable see service instructions for boiler control unit Parts lists Parts list 5692849 Components...

Страница 23: ...Sensor well boiler water temperature sensor 020 Cleaning brush wearing part 021 Brush handle 022 Extension piece 023 Turbulator extractor 224 Cover sensor coupling Information on position 103 Rated h...

Страница 24: ...24 201 204 225 213 214 213 227 226 200 200 202 203 212 210 208 206 206 201 206 206 Fig 9 Parts lists Parts list 5692849 Components...

Страница 25: ...ont panel bottom 206 Side panel 208 Centre rail 210 Rail front left 212 Rail back left 213 Thermal insulation jacket 214 Thermal insulation jacket centre only for 1100 to 1950 kW 225 Thermal insulatio...

Страница 26: ...219 223 218 203 205 217 216 215 206 211 209 207 206 208 B 222 220 A 228 307 Fig 10 A Type plate B Boiler control unit see service instructions for boiler control unit Parts lists Parts list 5692849 C...

Страница 27: ...l back right 215 Thermal insulation mat back 216 Thermal insulation mat back left 217 Thermal insulation mat back right 218 Mounting bracket rear 219 Mounting bracket 220 Trunking retainer 221 Cable t...

Страница 28: ...ler systems apply the out put of the smallest boiler When designing the system observe the following Install shut off valves in each section This prevents the need for draining all the heating water i...

Страница 29: ...g the annual service See the relevant section in the chapter on commission ing inspection and maintenance Avoid the use of gas permeable components e g per meable plastic pipes in underfloor heating s...

Страница 30: ...regulations Solder connections should preferably be made with Ag or Cu hard solder If liquids containing chlorides are used for soft soldering any deposits must be removed from the circuit afterwards...

Страница 31: ...enance service Commissioning Maintenance service Maintenance service Date By Commissioning Maintenance service Maintenance service Date By Commissioning Maintenance service Maintenance service Date By...

Страница 32: ...32 Commissioning Maintenance service Maintenance service Date By Commissioning service reports Maintenance service cont 5692849 Appendix...

Страница 33: ...60 C At rated heating output C 180 At partial load 60 C 125 Temperature at a boiler water tempera ture of 80 C C 195 Product ID CE 0085BQ0020 Standard seasonal efficiency to DIN for operation with fue...

Страница 34: ...t part of ordi nary household waste For decommissioning the system isolate the system from the power supply and allow components to cool down where appropriate All components must be disposed of corre...

Страница 35: ...energy efficiency of heating and ventilation systems in buildings to DIN V 4701 10 which is specified by the EnEV Germany This product meets the requirements of the Efficiency Directive 92 42 EEC Manu...

Страница 36: ...ments 16 P Parts Ordering 17 Parts list 1600 to 1950 kW 20 700 to 1300 kW 18 Pressure switch function checking 12 Product information 6 Pump controlled pressure maintaining systems 12 R Requirements f...

Отзывы: