11
Boiler connections (cont.)
Boiler size
6
7
8
9
Steam connector
for permiss. operating pressure
6 bar
PN 16 DN
125
125
150
150
8 bar
PN 16 DN
100
100
125
150
10 bar
PN 16 DN
80
100
125
125
PN 40 DN
—
—
—
—
13 bar
PN 40 DN
80
80
100
100
16 bar
PN 40 DN
65
80
80
100
18 bar
PN 40 DN
65
65
80
100
20 bar
PN 40 DN
65
65
80
80
22 bar
PN 40 DN
65
65
65
80
25 bar
PN 40 DN
50
65
65
80
Safety valve connector
for permiss. operating pressure
6 bar
PN 40 DN
40
40
50
50
8 bar
PN 40 DN
32
40
40
50
10 bar
PN 40 DN
32
32
40
40
13 bar
PN 40 DN
25
32
32
40
16 bar
PN 40 DN
25
25
32
32
18 bar
PN 40 DN
20
25
32
32
20 bar
PN 40 DN
20
25
25
32
22 bar
PN 40 DN
20
25
25
32
25 bar
PN 40 DN
20
20
25
25
Feedwater connector
for permiss. operating pressure
6-25 bar
PN 40 DN
32
32
32
32
Fitting the test and control equipment
Fit test and control equipment that is
pressure tested to the same level as the
operating pressure of the boiler and that
is suitable for the intended operating
mode (operation with or without constant
supervision). Agree details with the
responsible approval body, which should
also approve them.
Note
Carry out the installation in accordance
with the instructions supplied with the
equipment.
For the electrical connection, see the
connection and wiring diagrams provi-
ded.
Connecting the boiler on the steam side
(cont.)
5607 279 GB