Vitoflex 300-RF Installation & Operating
Operating the Boiler
Heating up
- Press the F1 key “Vitoflex 300-RF Wood”. The loader
modules will be switched on in the appropriate order.
When there is enough fuel in the combustion chamber,
the entire loader system switches off.
- The automatic ignition then takes place. The ignition
process stops as soon as the fire is started.
Operation
- The wood fuel is supplied depending on the light
barriers in the metering container and in the
combustion chamber, allowing for residual oxygen.
- The primary and secondary air vents adjust the air
flow depending on the flue gas temperature and
residual
oxygen.
- With the setting “Storage Management, Temperature,
Storage, Average”, it is possible to keep the facility
in continuous high-performance operation for as long
as possible - with fewer ignitions, better efficiency and
lower
emissions.
(Only possible with storage tank management option)
- When the boiler temperature set point is reached, the
facility switches to “Run Auger Empty”. When the
in-feed auger has been run empty, and the flue gas
temperature is less than 194°F (90°C), the flue gas
exhaust blower switches off and the air vents close.
- When the “System Temperature Setting” is fallen below
the set point, the boiler will automatically start back up.
Switching off
- Press the F1 “Vitoflex 300-RF Wood”. As feedback to
this, “Run Auger Empty” will appear on the control
panel.
CAUTION
DO NOT use the main switch to switch off (DANGER OF
BACK BURN)!
Operation