2.2 Specification
Specification
Rated heating output
kW
390
530
720
950
1250
Min. heat transfer
kW
117
159
216
285
375
Fuel efficiency
kW
424
576
783
1033
1359
Performance data
Rated heating output with standard fuel M45
*1
kW
390
530
720
950
1250
Rated constant heating output with standard
fuel M45
*2
kW
370
503
648
855
1125
Minimum heating output Q
min
*3
kW
117
159
216
285
375
Heating data
Flow temperature
– Permissible
*4
(safety temperature)
°C
100
100
100
100
100
– Maximum
*5
°C
95
95
95
95
95
– Minimum
*5
°C
75
75
75
75
75
Minimum return temperature
°C
65
65
65
65
65
Permiss. operating pressure
Boiler
bar
6
6
6
6
6
MPa
0.6
0.6
0.6
0.6
0.6
Test pressure
bar
8.6
8.6
8.6
8.6
8.6
MPa
0.86
0.86
0.86
0.86
0.86
Safety heat exchanger
bar
3 - 6
3 - 6
3 - 6
3 - 6
3 - 6
MPa
0.3 - 0.6
0.3 - 0.6
0.3 - 0.6
0.3 - 0.6
0.3 - 0.6
Thermally activated safety valve
l/h
-
-
-
-
-
Water flow rate
Flow rate (10 K diff.)
m³/h
33.54
45.58
61.92
81.70
107.50
Flow rate (15 K diff.)
m³/h
22.36
30.39
41.28
54.47
71.67
Flow rate (20 K diff.)
m³/h
16.77
22.79
30.96
40.85
53.75
Pressure drop on the water side
Pressure drop on the water side (10 K diff.)
Pa
2314
4274
7888
5844
10118
Pressure drop on the water side (15 K diff.)
Pa
1029
1900
3506
2597
4497
Pressure drop on the water side (20 K diff.)
Pa
579
1069
1972
1461
2529
Heating surface
m
2
25.44
33.88
49.47
66.75
79.04
Total dimensions
Total length
mm
4370
4870
5257
5447
5992
Total width (boiler)
mm
1274
1247
1380
1612
1612
Total width (boiler with feed screw conveyor)
mm
2382
2382
2488
2852
2852
Total height (boiler)
mm
2378
2536
2834
3035
3230
Total height (boiler with flue gas fan)
mm
3186
3186
3378
3452
3717
Weight
Boiler
kg
1680
2707
3291
4874
5563
Combustion block
kg
2970
4238
4953
5779
6520
Displacer rods
kg
-
-
394
538
538
Flue gas fan
kg
60
62
78
82
107
Feed screw conveyor
kg
153
153
153
190
190
Total dry weight
kg
4863
7160
8869
11463
12919
Total wet weight
kg
6076
8604
10730
13406
15400
Capacity
Boiler water
l
1213
1444
1861
1943
2482
Content on hot gas side
l
1540
2280
2830
4050
5210
Ash box, grate ash
l
240
240
240
240
240
Ash box, flue gas dust extractor
l
240
240
240
240
240
*1
When the boiler and combustion chamber have been cleaned and the boiler is equipped with pneumatic boiler cleaning.
*2
Levelled output when boiler is used as base load boiler in continuous operation, equipped with pneumatic boiler cleaning and a runtime
(time between 2 boiler cleaning operations) of 600 hours
*3
Q ≥ Q
min
: Output operation modulating control (variable output control)
Q ≤ Q
min
: Low load with ON Q
min
/ OFF (stop and go operation)
*4
Shutdown temperature of the high limit safety cut-out
*5
Temperature adjustable at the control unit
Vitoflex 300-UF
(cont.)
14
Viesmann
VITOFLEX 300-UF
2
5682428