Vitoflex 300-UF Technical Data
Electrical
Ecocontrol - Accessories for Output Management
Thermal storage tank management, 5 sensors
Modulating output operation of the Vitoflex 300-RF
is optimized with the use of a thermal storage tank.
Short term heat demand peaks are also covered. The
temperature sensors record the heating of the thermal
storage tank. The specification of the charging level of
the thermal storage tank is weather-compensated and
carried out via the outside temperature sensor. The
combustion heat output is matched to the charging level
of the heating water thermal storage tank.
Standard delivery:
5 Pt1000 sensors with sensor well
b
in. x 12 in.
(280
mm)
1 Pt1000 outside temperature sensor
Note:
Controller module and data cable required
External demand ON/OFF
Input for automatically switching the system on/off via
an external floating N/O contact
Output signal 0 - 10 V
Issuing of boiler output as voltage signal and a connection
to receive a maximum boiler output limit included in
standard delivery.
Functions:
Issue of the output signals
Receipt and processing of an external output restriction
Note:
The installation of “Output signals 0 – 10 V”
is possible irrespective of additional control modules
used.
Thermal storage tank management 5 sensors not possible.
Note:
The boiler can only be shut down externally via
“External demand ON/OFF”. This should be
ordered separately.