46
Check that the earth cable is connected to the protec-
tive magnesium anode.
Note
We recommend checking the function of the protective
magnesium anode annually. This function test can be
carried out without interrupting operation, by measur-
ing the earth current with an anode tester.
C B
A
Fig. 39
1.
Remove cover
A
(two-part design up to 26 kW).
2.
Remove earth cable
B
from tab
C
.
3.
Connect tester (up to 5 mA) in series between tab
C
and earth cable
B
.
■
If the current measures > 0.3 mA the protective
magnesium anode is OK.
■
If the current measures < 0.3 mA or if there is no
current at all, inspect the protective magnesium
anode visually (see page 48).
Draining the boiler on the DHW side
1.
Shut off the DHW supply upstream of the appli-
ance.
Commissioning, inspection, maintenance
Checking the anode connection and anode earth current with an anode
tester