2.2 Specification
Gas boiler, type B and C, category II
2N3P
Type
B2LE
Rated heating output range (to EN 15502-1)
T
F
/T
R
= 50/30 °C
Natural gas
kW
1.9 - 11.0
1.9 - 19.0
1.9 - 25.0
1.9 - 32.0
LPG
kW
2.5 - 11.0
2.5 - 19.0
2.5 - 25.0
2.5 - 32.0
T
F
/T
R
= 80/60 °C
Natural gas
kW
1.7 - 10.1
1.7 - 17.4
1.7 - 22.9
1.7 - 29.3
LPG
kW
2.2 - 10.1
2.2 - 17.4
2.2 - 22.9
2.2 - 29.3
Rated heating output for DHW heating
Natural gas
kW
1.7 - 21.8
1.7 - 26.2
1.7 - 30.4
1.7 - 33.5
LPG
kW
2.2 - 21.8
2.2 - 26.2
2.2 - 30.4
2.2 - 33.5
Rated heat input
Natural gas
kW
1.8 - 22.7
1.8 - 27.3
1.8 - 31.7
1.8 - 34.9
LPG
kW
2.3 - 22.7
2.3 - 27.3
2.3 - 31.7
2.3 - 34.9
Product ID
CE-0085CT0017
IP rating
to EN 60529
IP X1
Gas supply pressure
Natural gas
mbar
kPa
20
2
20
2
20
2
20
2
LPG
mbar
kPa
50
5
50
5
50
5
50
5
Max. permiss. gas supply pressure
*5
Natural gas
mbar
kPa
25.0
2.5
25.0
2.5
25.0
2.5
25.0
2.5
LPG
mbar
kPa
57.5
5.75
57.5
5.75
57.5
5.75
57.5
5.75
Sound power level
(to EN ISO 15036-1)
– At partial load
dB(A)
32
32
32
32
– At rated heating output (DHW heating)
dB(A)
41
47
49
52
Power consumption
in the delivered condition
(incl. circulation pump)
W
37
47
68
110
Weight
– Excl. heating water and DHW
kg
67.8
67.8
67.8
67.8
– Incl. heating water and DHW
kg
120.0
120.0
120.0
120.0
Water capacity
(excl. diaphragm expansion
vessel)
l
3.0
3.0
3.0
3.0
Max. flow temperature
°C
82
82
82
82
Max. flow rate
(Limit for the use of hydraulic separation)
l/h
See residual head graphs
Nominal circulating water volume
At T
F
/T
R
= 80/60 °C
l/h
473
818
1076
1374
Expansion vessel
Capacity
l
10
10
10
10
Pre-charge pressure
bar
0.75
0.75
0.75
0.75
kPa
75
75
75
75
Permiss. operating pressure
bar
3
3
3
3
MPa
0.3
0.3
0.3
0.3
Connections
(with connection accessories)
Boiler flow and return
R
¾
¾
¾
¾
Cold water and DHW
G
½
½
½
½
Dimensions
Length
mm
500
500
500
500
Width
mm
600
600
600
600
Height
mm
950
950
950
950
Gas connection
(with connection accessories)
R
¾
¾
¾
¾
DHW loading cylinder
Capacity
l
46
46
46
46
Permiss. operating pressure (DHW side)
bar
10
10
10
10
MPa
1
1
1
1
*5
If the gas supply pressure is higher than the maximum permissible value, install a separate gas pressure governor upstream of the sys-