F.378

Burner in a 

fault state

Flame loss during 

stabilization or 

operating phase

  Check gas supply (gas pressure and gas flow switch).

  Check flue gas recirculation.

  Check for contamination of ionization electrode and burner gauze assembly. Reset the boiler.

F.379

Burner in a 

fault state

Flame signal 

not present or 

insufficient

  Check ionization electrode connecting 

     cable for damage and firm seating.

  Check ionization electrode; replace if necessary. Reset the boiler.

F.380

Burner in a 

fault state

Flame loss 

immediately after 

flame formation 

(during safety time)

Check gas supply (gas pressure and gas flow switch).

Check balanced flue system for flue gas recirculation.

Check ionization electrode and burner gauze assembly:

  Clearance to burner gauze assembly

  Contamination on electrode Reset the boiler.

F.381

Burner in a 

fault state

Flame loss during 

operating phase

Check gas supply (gas pressure and gas flow switch).

Check balanced flue system for flue gas recirculation.

Check ionization electrode and burner gauze assembly:

  Clearance to burner gauze assembly.

  Contamination on electrode Reset the boiler.

F.446

Burner in a 

fault state

Deviation, boiler 

supply temperature 

sensor/high limit 

safety cutout

Check the supply temperature sensor/high limit safety cut-out.

Check plug-in connection and lead to sensor.

Reset the boiler.

F.467

Burner in a 

fault state

Gas supply 

insufficient 

during calibration. 

Contaminated or 

insufficiently sized 

gas line.

  Test static gas pressure and gas flow 

     pressure.

  Check that on-site gas line and gas flow 

     switch are correctly sized.

  Visually inspect gas solenoid valve inlet and 

     strainer on the inlet side for contamination. Reset the boiler.

Note:

 Contamination from a brazed gas line, for example, 

can block up the gas solenoid valve strainer on the inlet side.

 

  

 

Fault Codes

Fault Codes

28

Displayed 

fault code

System 

characteristics

Cause

Measures

F.13

Regulates as 

if the outside 

temperature 

were 0°C.

Lead break, outside 

temperature sensor

  Check the operating mode setting in the commissioning assistant and correct if necessary.

  Check outside temperature sensor and connection to sensor (external plug, contacts 1 and 2).

  Measure voltage at sensor input on electronics module. 

     Target value: 3.3V– with sensor disconnected. Replace faulty component if necessary.

F.69

Burner in a 

fault state

Ionization current 

lies outside the 

permissible range

Check ionization electrode:

  Check whether insulation block is touching electrode ceramic.

  Check gas solenoid valve: Activate 

     “Minimum heating output” for approx. 4 min in actuator test.

     If this causes a fault to occur, replace BCU burner control unit.

  In the actuator test, switch from “Minimum heating output” to “Maximum heating output”. ‘

     If this fault occurs during modulation, check the intake screen for contamination. 

Replace the fan unit if necessary.

F.70

Burner in a 

fault state

Internal error burner 

control unit

Replace BCU burner control unit:

See page 89.

F.71

Burner in a 

fault state

Fan speed too low

  Check fan for blockage.

  Check the gas type and flue system setting in the commissioning assistant and correct if necessary.

Reset the boiler.

F.72

Burner in a 

fault state

Fan idle state not 

reached

Reset the boiler.

If fault occurs repeatedly, replace fan unit.

F.73

Burner in a 

fault state

Internal 

communication error

Reset the boiler.

If fault recurs, replace BCU burner control unit: See page 89.

F.182

No DHW 

heating

Short circuit, outlet 

temperature sensor 

(if installed)

Check outlet temperature sensor (plug X1, cores 13 and 14). 

Measure sensor input on electronics module. 

Target value: 3.3V– with sensor disconnected

F.183

No DHW 

heating

Lead break, outlet 

temperature sensor 

(if installed)

Check outlet temperature sensor

(plug X1, cores 13 and 14).

F.299

Time/date 

incorrect

Real time clock 

setting incorrect

Set the time and date.

F.373

Burner in a 

fault state

Heat transfer 

too low during 

calibration

Temperature limiter 

has shut down.

  Ensure adequate heat transfer.

  Check circulation pump for faults, scale or blockages.

  Check 3-way diverter valve function in actuator test. Vent the system.

  Check function of flow sensor. Reset the boiler.

Note:

 Fault messages dependent on boiler equipment level

Refer to the fault code section of the B2HE Service Instructions for 

the complete list of fault codes.

Содержание VITODENS 200-W B2HE 150

Страница 1: ...es for Canada For U S installations use the National Fuel Gas Code ANSI Z223 1 Always use latest editions of codes In Canada all electrical wiring is to be done in accordance with the latest edition o...

Страница 2: ...Boiler pressure relief valve PRV and pressure gauge I Low loss header accessory J Boiler fill K Indirect DHW tank L Expansion tank Low loss header Viessmann optional accessory Boiler Boiler Condensate...

Страница 3: ...Equivalent length 87 elbow 87 inspection tee 1 6 ft 0 5 m 45 elbow 1 ft 0 3 m Refer to the Rigid and Flex Pipe Venting Systems Instructions supplied Flue Connection for Single or Two Pipe Systems Flu...

Страница 4: ...with the control base clips Opening the junction box 4 Release junction box cover clamps 5 Lift the junction box cover Legend A Diaphragm grommets low voltage B ON OFF switch C Knockouts for 120VAC c...

Страница 5: ...o 3 zone circuits Each zone circuit includes input output for one pump and one thermostat 24VAC or Dry Contact field supplied For systems with primary secondary loops using Low Loss Header or Closely...

Страница 6: ...iler application Heating circuits with mixing valve or heating circuits with mixing valve with external hook up if installed DHW Not available Tank with one sensor Tank with one sensor and DHW circula...

Страница 7: ...the Room Temperature 25 Setting the Room Temperature Setting the Room Temperature 26 Setting DHW Temperature Setting DHW Temperature 27 1 Taap the header bar and select desired heating circuit 2 Tap 3...

Страница 8: ...ere 0 C Lead break outside temperature sensor Check the operating mode setting in the commissioning assistant and correct if necessary Check outside temperature sensor and connection to sensor externa...

Отзывы: