33
Commissioning assistant
sequence
Explanations and references
Commissioning
"C.1"
Filling program
ON = on
OFF = off
Note
It is possible to interrupt or end the process while a rotating rectangle alternat-
ing with the current system pressure is displayed; to do so, press and hold
for 3 s.
"C.2"
Venting program
ON = on
OFF = off
Note
It is possible to interrupt or end the process while a rotating rectangle alternat-
ing with the current system pressure is displayed; to do so, press and hold
for 3 s.
"C.3"
Gas type
2 - Natural gas CPG
3 - Liquid gas LPG
"C.5"
Flue system
1 - Open flue 60 mm
2 - Room sealed 60/100 mm
3 - Open flue 80/125 mm
4 - Room sealed 80/125 mm
"C.6"
Flue length
Given in full metres (round up if necessary)
Note
An additional length of 1 m must be factored in for every flue bend.
"C.7"
Operating mode
1 - Constant operation with time program
4 - Weather-compensated
13 - Constant operation with optional room thermostat
14 - OpenTherm
15 - Individual room control
16 - Individual room control with modulation
Note
Operating modes 15 and 16 can only be set via the software tool.
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
6167586
Содержание Vitodens 100-W B1HF Series
Страница 14: ...14 1 4 5 3 2 Fig 4 Installation sequence Removing the boiler from the packaging 6167586 Installation ...
Страница 30: ...30 1 2 Fig 22 Installation sequence Fitting the front panel 6167586 Installation ...
Страница 87: ...87 1 2 4 3 7 5 6 Fig 48 Troubleshooting Repairs cont 6167586 Diagnosis ...
Страница 107: ...107 6167586 ...