40
5784 568 - 03
Vitodens 100-W, B1HA series & B1KA Combi Installation/Service
CAUTION
Unsuitable fill water increases the level of deposits and
corrosion, and may lead to damage to the equipment.
Thoroughly flush the entire heating system prior to
filling with water.
Only use fill water of potable quality.
Soften fill water harder than 150 ppm temporary
hardness.
Inhibitors or antifreeze additives suitable for heating
systems may be added manually.
Filling and Bleeding the Heating System
Start-up, Inspection and Maintenance
4.
/
until CONFI flashes.
5. OK to confirm.
“P” appears in the left hand display area. The right
hand display area flashes.
6. Use
/
to select “12”.
7. OK to confirm.
“1” flashes in the left hand display area.
8. OK to confirm.
“0” flashes in the right hand display area.
9. Use
/
to select “1”.
10. OK to confirm.
Filling is activated. The boiler circuit pump is running,
the 3-way diverter valve moves to its centre position.
This function terminates automatically after 30 min.
or when the ON/OFF switch is switched off.
Activating boiler pump (bleeding program)
1. Close the gas shut-off valve.
2. Switch ON the power supply.
3. Tap MODE.
Item # Function
Setting Options
Description
Default
Setting
1
Filling
(see page 40)
0 - Fill mode OFF
After pressing ‘OK’ the filling function is active. This
process will automatically terminate after 30 min.
0
1 - Fill mode ON
2
Reduce max.
heating output
(see page 45)
00 -Low fire (25%)
The max. heating output can be adjusted according
to the requirements of the system. The adjusted
heating output should be tested by measuring the gas
throughput.
00
26-99 - Modulation Range
(26-99%)
100 - High fire (100%)
3
Altitude setting
(see page 45)
0 - < or = 5000 ft (1500 m) Adjusts the boiler for high altitude operation.
0
1-5 - Do Not Adjust
6 - > 5000 ft (1500 m)
4
Do not adjust!
--
--
0
5
Fuel Type
(see page 42)
0 - Natural Gas
The gas type can be converted from natural gas to LPG.
Conversion kit is required.
0
1 - LPG
6
Do not adjust!
--
--
0
7
Parameter reset
1 - Vitodens 100-W B1KA-35 The parameter is fixed based on the boiler type and size.
When replacing the boiler control, refer to boiler rating
on the boiler to set model and size. After adjusting
the parameter cycle the boiler power and verify the
parameter setting.
#
2 - Vitodens 100-W B1HA-26
3 - Vitodens 100-W B1HA-35
4-99 - Do Not Adjust
8
Outdoor Temp.
Sensor
0 - NTC 10K Ohm
The right outside temp. sensor has to be adjusted.
0
1 - Do not Adjust
9
Button Tone
0 - On
The signal tone for display operation can be switched
off.
0
1 - Off
10
Backlight Display
- Standby Mode
0 - Dimmed
The display backlighting for standby is either dimmed or
off.
0
1 - Off (no back)
11
Display Contrast
0-6
The display contrast is adjustable from 0 to 6. The
higher the value, the greater the contrast.
3
12
Eco/Comfort
(B1KA Only)
(see page 46)
0 - Eco
The comfort function makes DHW available faster at the
selected set DHW temperature. Only available Vitodens
100-W B1KA
0
1 - Comfort
13
Temperature Unit
(see page 46)
0 - °C
The temperature displayed can be set to °C (Celsius) to
°F (Fahrenheit).
1
1 - °F
14
DHW sensor type
(B1HA)
(see page 46)
0 - DHW Temp. Sensor (NTC
10K Ohm)
The boiler either works with a tank sensor (NTC
10kOhm - Supplied) or with a tank aquastat (field
supplied)
0
1 - Aquastat (Dry Contact)
Setup Menu Overview