31
Room sealed operation
7
60 mm coaxial
Correction fac-
tor
0
1
2
3
4
5
6
Rated heating
output (kW)
Flue length (m)
24
≤ 4 > 4 ≤ 8
> 8 ≤
12
> 12 ≤
15
Do not adjust
33
≤ 4 > 4 ≤ 7
> 7 ≤
11
> 11 ≤
20
Do not adjust
Burner adjustment when connecting multiple flues to a flue sys-
tem
When connecting several
Vitodens 050-W to a shared flue system:
Adjust the burner setting of each con-
nected boiler by a correction factor to
match the flue system.
System conditions:
■ Shared flue in shaft
7
100 mm
■ Balanced flue connection pipe from
boiler to shaft
7
80/125 mm
■ Minimum shaft cross-section
– Square 175 x 175 mm
– Round
7
195 mm
■ Height between floors min. 2.5 m
■ Max. 4 boilers with the same rated
heating output connected to the flue
system
1.
Press MODE and simultaneously
for 3 s.
"SERV"
is displayed and
"I"
flashes.
2.
Use / to select
"4"
and confirm with
OK.
"0"
flashes on the display.
3.
Look up the required correction factor
relevant to the flue system require-
ments in the tables below.
4.
Use / to set the required correction
factor and confirm with OK.
5.
Press MODE and simultaneously
for 3 s.
Service mode is terminated. Service
mode also terminates automatically
after 30 min.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)