Danger
If the trap is not full, flue gas can escape.
Escaping flue gas can cause life threatening
carbon monoxide poisoning.
Always fill the trap with water
before
commis-
sioning.
Connecting the neutralising system
Fig. 30
Neutralising system installation instructions
1.
Site the neutralising system either behind or adja-
cent to the boiler.
2.
Trim the condensate hose supplied to the required
length. Connect the condensate hose to the trap.
Connect the condensate hose to the neutralising
system with a constant fall.
3.
Connect the neutralising system to the drainage
system.
Note
Observe local waste water regulations.
Connections on the flue gas side
It is
essential
that a boiler flue connection (accesso-
ries) is used for connecting the flue outlet.
Fitting the trap
5833291