47
Coding in the delivered condition
Possible change
07:1
Boiler number in multi boiler sys-
tems (only for constant tempera-
ture control units)
07:2
to
07:4
Boiler number 2 to 4 in multi boiler
systems
08:...
Maximum burner heating output in
kW, in multi boiler systems
08:0
to
08:199
Maximum burner heating output ad-
justable in 1 kW increments, from 0
to 199 kW (limited by boiler-specific
parameters)
0D:0
Never adjust.
0E:0
Never adjust.
13:1
Never adjust.
14:1
Never adjust.
15:1
Never adjust.
21:0
No service interval set (in hours
run)
21:1
to
21:100
The number of hours run before the
burner should be serviced is adjust-
able from 100 to 10,000 h
One adjusting step
≙
100 h
23:0
No time set for burner service in-
terval
23:1
to
23:24
Interval adjustable from 1 to
24 months
24:0
"Service"
not shown on the dis-
play
24:1
"Service"
is shown on the display
(address is automatically set and
must be manually reset after a serv-
ice has been carried out)
28:0
No burner interval ignition
28:1
to
28:24
Time interval adjustable from 1 h to
24 h. The burner is force-started for
30 s at a time (only when operating
with LPG).
2E:0
Never adjust.
2F:0
Never adjust.
30:3
Boiler circuit pump speed-control-
led via 0 - 10 V interface
30:0
■
Connection of multi stage boiler
circuit pump
■
Operation with low loss header
(single or multi boiler system)
30:1
Boiler circuit pump speed-controlled
30:2
Boiler circuit pump speed-controlled
with flow rate
38:0
Burner control unit status: Opera-
tional (no fault)
38:≠0
Burner control unit status: Fault
DHW/Group "3"
Coding
Coding in the delivered condition
Possible change
56:0
Set DHW temperature adjustable
from 10 to 60 °C
56:1
Set DHW temperature adjustable
from 10 to above 60 °C
Code 2
Boiler/Group "2"
(cont.)
5792 925 GB
Codes