22
A
B
2.
1.
Fig. 14
A
Burner aperture
B
Combustion chamber
1.
Undo 3 screws. Remove locking bracket.
2.
Unscrew the inspection cover and remove.
3.
Clean the combustion chamber and heating surfa-
ces.
■
For normal cleaning, flush the heating surfaces
thoroughly with a jet of water.
■
For stubborn residues, surface stains or soot
deposits, cleaning agents can be used.
For this, observe the following:
–
Only use solvent-free cleaning agents. Ensure
that no cleaning agent gets between the boiler
body and the thermal insulation.
–
Remove soot deposits with alkaline cleaning
agents with surfactant additive.
–
Remove coatings and surface discolouration
(yellow-brown) with slightly acidic, chloride-free
cleaning agents based on phosphoric acid.
4.
Remove loosened deposits from the boiler. Flush
the heating surfaces thoroughly with a jet of water.
Cleaning agent manufacturer's instructions
5. Assemble in reverse order:
Position inspection cover, turn clockwise as far as
it will go by hand.
6.
Position the locking bracket. Apply thread-locking
fluid to the screws. Wind the screws in by hand as
far as they will go, then tighten by 1 turn.
Danger
Leaks can result in poisoning through escap-
ing flue gas.
Check the inspection cover is seated cor-
rectly.
Cleaning the condensate drain system
The condensate drain system comprises
■
Condensate drain
■
Trap
■
Neutralising system
■
All hoses or pipes running between these parts
Note
Clean the inside of the condensate drain system at
least annually.
Commissioning, inspection, maintenance
Cleaning the combustion chamber and heating…
(cont.)