iNSTALLATiON

iNST

ALL

A

Ti

ON

General Restrictions

a.   The highest hot or cold water draw off point should not exceed 10 metres above the 

Pressure Reducing Valve.

b.    An ascending spray type bidet or any other appliance with a Class 1 back-syphonage 

risk requiring a type A air gap should not be used.  

c.    Viessmann Vitocell 200 Cylinder should not be used where steam is the primary 

heating medium, or in a situation where maintenance is likely to be neglected.

d.   Unvented cylinders are not suitable  for use with solid fuel boilers.
e.   if the supply to the mixer fittings (other than a dual outlet type) is not taken 

from the balanced supply the system will become over pressurized and cause the 
pressure relief valve to discharge.  Over time this could also cause the premature 
failure of the appliance itself which will not be covered by the warranty,

f.     In larger properties with a number of bathrooms/en-suites and long pipe runs 

we would recommend that the balanced cold supply is provided with its own 
pressure reducing valve and is not taken from the balanced cold connection on the 
combination valve.  In this case it will also be necessary to fit a small expansion vessel 
on the balanced cold water system to accommodate the pressure rise caused by the 
increase in temperature of the balanced cold water.

g.   Check the performance requirements of the terminal fittings with regard to flow/

pressure are suitable.

Shower Fittings

Aerated taps are recommended to prevent splashing. Any type of shower mixing valve 
can be used as long as both the hot and cold supplies are mains fed.  However, all 
mains pressure systems are subject to dynamic changes particularly when other hot 
and cold taps/showers are opened and closed, which will cause changes in the water 
temperature at mixed water outlets such as showers.  For this reason and because 
these are now no more expensive than a manual shower we strongly recommend 
the use of thermostatic showers with this appliance.  These must be used in 3 storey 
properties where the impact on pressure/temperature of opening another tap in the 
system is greater than normal. The shower head provided must also be suitable for 
mains pressure supplies.

Pipe Layout

In all mains pressure installations it is important 
to  remember  that  the  incoming  cold  supply 
must be shared between all terminal fittings.  It 
is important that a 22mm supply is brought to 
the appliance and a 22mm take-off is continued 
at least to the bath.  If there are two baths, 28mm 
pipework should be considered.  One metre of 
smaller diameter pipework, or flow restrictors, 
should be provided on the final connection to 
all outlets so as to balance the water available.  
In any event the distribution pipework should 
generally be in accordance with EN806:1.

Plastic Pipework

This  appliance  is  suitable  for  use  with 
plastic  pipework  as  long  as  the  material 
is  recommended  for  the  purpose  by  the 
manufacturer and is installed fully in accordance 
with their recommendations.

Secondary Hot Water Circulation

Some models are fitted with a secondary return 
tapping  as  standard  (see  table  1  for  details).  
If  fitted,  an  extra  expansion  vessel  may  be 
necessary.  A non-return valve MUST be FITTED 
near the return connection.  No valve or terminal 
fitting  should  be  installed  between  the  non 
return valve and the cylinder. (See schematic 
arrangement on page 13.)

INCOMING COLD SUPPLY

M

DC

DC

DC

TO
EXTERNAL
TAP

SINK

WATER SOFTENER (IF NECESSARY)

WM or DWM

WHB

W.C.

DC

DC

SH

DHW

WHB

WC

BATH

SCV

SCV

P&T

ERV/NRV

PRV

DCV

Note:  
Cold supplies to single taps must be 

taken  from  the  mains  cold  water 

system.
Cold supplies to mixer taps must be 

taken from the balanced cold water 

connection  on  the  combination 

valve.

Содержание Vitocell 200 Cylinder

Страница 1: ...Document G3 and manufactured in accordance with BS EN 12897 the specification for unvented water storage vessels in the interest of continuously improving the Vitocell 200 Cylinder range Viessmann reserve the right to modify the product without notice and in these circumstances this booklet which is accurate at the time of printing should be disregarded ...

Страница 2: ...s provided to assist generally in the selection of equipment Responsibilityforselectionandspecificationofourequipmentmusthoweverremainthat of our customer and any experts or consultants concerned with the installation s Please note that we do not therefore accept any responsibility for matters of design selection or specification for the effectiveness of an installation or system containing one of...

Страница 3: ...route should be even In apartment buildings containing a number of storeys we would recommend that the appliances are moved vertically in a mechanical lift If it is proposed to use a crane expert advice should be obtained regarding the need for slings lifting beams etc A specific manual handling assessment is shown in Appendix B at the rear of this manual Maintenance Modifications should not be ma...

Страница 4: ...or use with gas or oil boilers Figure 1 Vitocell 200 Cylinders must not be used with solid fuel boilers or steam as the energy source 2 ViessmannVitocell 200 B Solar Cylinder For providing hot water by solar gains and gas or oil boilers Figure 2 Unvented cylinders must not be used with solid fuel boilers or steam as the energy source Viessmann Vitocell 200 V Cylinder ViessmannVitocell200 VCylinder...

Страница 5: ...ith a sealed heating system the boiler must incorporate its own energy cut out overheat thermostat A high efficiency second solar coil is positioned below the primary coil to ensure maximum benefit of solar gain energy ViessmannVitocell 200 B Solar Cylinder models are listed in Table 1 on Page 6 7 Note The cold supply elbow c w drain tapping must be fitted as shown in figs 1 2 3 and 4 A flexible h...

Страница 6: ...r Litres A mm mm B mm C mm D mm E mm F mm Litres G mm H mm Vitocell 200 V 90 19 109 90 3 12 732 550 490 n a 352 367 n a 40 367 367 120 22 142 120 3 12 920 550 678 n a 352 367 n a 67 367 367 150 26 176 150 3 18 1107 550 865 n a 392 442 n a 92 407 407 180 28 208 180 3 18 1295 550 1053 n a 432 442 n a 116 447 447 210 33 243 210 3 24 1483 550 1241 1127 432 442 n a 145 482 482 250 38 288 250 3 24 1733 ...

Страница 7: ... a n a n a 16 5 0 59 0 165 n a n a 21 16 0 80 n a 367 367 223 312 n a n a n a n a n a 18 0 59 0 165 n a n a 27 19 1 00 n a 407 407 223 392 n a n a n a n a n a 18 5 0 68 0 191 n a n a 28 19 1 20 n a 447 447 223 392 n a n a n a n a n a 19 0 78 0 216 n a n a 33 21 1 40 n a 482 482 223 392 n a n a n a n a n a 20 5 0 78 0 216 n a n a 41 26 1 60 n a 577 577 223 472 n a n a n a n a n a 21 5 0 97 0 241 n ...

Страница 8: ...rimary return 22mm 10 Primary flow 22mm Component kit supplied separately A Combination inlet group incorporating pressure reducing valve strainer check valve balancecoldtakeoffpoint expansion reliefvalveandexpansionvesselconnection points B Potable expansion vessels c w flexible hose and wall bracket C Tundish D Dual control thermostat and combined overheat thermostat E Two port 22mm zone valve f...

Страница 9: ...el collector 22mm compression 11 Solar coil flow from panel 22mm compression 12 Solar thermostat pocket Component kit supplied separately A Combination inlet group incorporating pressure reducing valve strainer check valve balance cold take off point expansion relief valve and expansion vessel connection points B Potable expansion vessels c w flexible hose and wall bracket C Tundish D Dual control...

Страница 10: ... of 40 litres min in most conditions Flow rates for ALL mains pressure systems are subject to district pressures and system dynamic loss Particularly on larger properties with more than one bathroom the pipe sizes should be calculated in accordance with BS6700 Model Selection Where selecting a solar model it is important to checkthededicatedsolarvolume shownintables1 2 issuitableforthetotalfloorar...

Страница 11: ... at mixed water outlets such as showers For this reason and because these are now no more expensive than a manual shower we strongly recommend the use of thermostatic showers with this appliance These must be used in 3 storey properties where the impact on pressure temperature of opening another tap in the system is greater than normal The shower head provided must also be suitable for mains press...

Страница 12: ...ed as close as possible and within 500mm of the safety device e g the temperature relief valve Thedischargepipe D2 fromthetundishshould terminate in a safe place where there is no risk to persons in the vicinity of the discharge be of metal and a Be at least one pipe size larger than the nominaloutletsizeofthesafetydeviceunless its total equivalent hydraulic resistance exceeds that of a straight p...

Страница 13: ...tems are installed where dischargesformsafetydevicesmaynotbeapparenti e indwellingsoccupiedby blind infirmordisabledpeople considerationshouldbegiventotheinstallation of an electronically operated device to warn when discharge takes place Safety ThesafetydevicessuppliedorfittedonanViessmannVitocell200Cylinderareselected for their suitability for the temperatures and pressures involved They must no...

Страница 14: ...st be in accordance with the relevant IEE Wiring Regulations and the circuit must be protected by a suitable fuse and a double pole isolating switch The correct method of terminating the wiring to the immersion heater is shown opposite Line Strainer This is integral within the combination inlet group to reduce the likelihood of contaminants fouling the valve seat Following installation this line s...

Страница 15: ...le check valve or some other no less effective backflow prevention device is permanently connected at the inlet to the circuit and the temporary connection is removed after use Alternatively a CA device can be used which will allow the system to be permanently connected to the cold mains supply The primary system can then be topped up when required in the same way as an open vented system fitted w...

Страница 16: ...ple or animals below if the valve were to release scalding water and steam The pipe leading to the safety device and the collectorshouldbeofrigidandnon deformable construction without any possibility of restriction or disclosure by any other fitted component A more detailed diagram of our recommended arrangement for a typical solar system is shown on page 18 The Viessmann solar controller Solar Di...

Страница 17: ...The diagrams opposite shows how the blending valve can be piped onsite Figure 1 shows the cold water port of the blending valve connected to the mains cold water supply before the inlet control group This arrangement is completely unacceptable and illegal because the water is allowed to expand in to mains cold water supply the vessel will be charged to the incoming mains supply which may be consid...

Страница 18: ...Solar Cylinder T Anti Gravity Check Valve Pressure Relief Valve Anti Gravity Check Valve Standard 10 way wiring junction box Not supplied No isolation valve should be installed between the solar circuit and the safety valve pressure relief valve Vitosolic 100 Type SD1 21 20 19 18 17 16 L N R1 N R2 N 15 14 13 12 11 10 9 6 5 4 3 2 1 S1 S2 S3 PWM 145 Schematic Showing Solar Wiring Requirements ...

Страница 19: ...Orange Yellow White Red B Or Y Wh R Br Bl G Y Br Br Bl G Y Or Gr 5 Amps Br Bl G Y Br Br B Br Bl G Y Br B Bl Br Br Br Br Bl B G Y G Y Br Br Blue core used from standard 3 core flex please ensure you use brown sleeving at both terminating ends to identify core potential 3 core flex 4 core cable L N L L_P SL_B E N N_P E_P Br Bl G Y B Br Bl G Y Boiler Pump ISSUE No 3 APPROVED DRN DATE 23 09 09 S Gator...

Страница 20: ...quately flushed and refilled with the mains water immediately on completion of the disinfection procedure Damage caused through a failure to do this adequately will not be covered by the warranty For the above reasons we recommend the use of a non chlorine dased disinfectant such as Fernox LP Sterox as manufactured by Cookson Electronics when carrying out disinfection of systems incorporating thes...

Страница 21: ...d which disappears as the pressure in the system stabilises This is quite normal with these types of systems and does not indicate a fault In some areas the water will initially appear cloudy but will quickly clear when left to stand This is nothing to be concerned about and is due to aeration of the water WARNING Ifwaterisseenflowingthroughthetundish thisindicatesafaultcondition which needs actio...

Страница 22: ...ng any water 5 Check the condition and if necessary descale the heat exchangers in hard water areas 6 Check that water pressure downstream of pressure reducing valve is within the manufacturer s limits 7 Check operation of motorised valve 8 Check the pressure on the air side of the expansion vessel This must be done when the water in the cylinder is cold 9 Checkandadvisethehouseholdernottoplaceany...

Страница 23: ...If the units are not getting hot and the heat source is electrical ensure that the immersion heaters are isolated from the mains before re setting the energy cut out If the immersion heater s need replacing this should be done with the units supplied from Viessmann Limited Discharge From Relief Valves If cold water is discharging from the expansion relief valve into the tundish check the pressure ...

Страница 24: ...umbing is correct Re set Is all wiring to the controls ok Replace thermostat Re wire START Is boiler on Is hot water programmer in on position Is zone valve in correct position Is control temperature set at 55ºC 60ºC Has high limit cut out Re set END YES YES YES YES YES YES YES NO NO NO NO NO NO NO ...

Страница 25: ...rom restrictions blockages YES NO Is pressure reducing valve in combination valve working Fault Poor Water Flow At Hot Taps Fault Water Discharge Into Tundish Clean or replace as required Is expansion vessel charge pressure correct Replace ERV TPRV Replace PRV END START Is pressure downstream of pressure reducing valve correct Is valve seal and seat clean undamaged Is heater operating at less than...

Страница 26: ...alve set at 4 75 bar 1 SG010 5 flexible hose 1 SG003 7160757 7 12 litre expansion vessel 1 XG190 8 18 litre expansion vessel 1 XG191 9 24 litre expansion vessel 1 XG192 10 Wall mounting bracket for 12 18 24 litre expansion vessel 1 XG184 11 35 litre expansion vessel 1 XG193 12 Wall mounting bracket for 35 litre expansion vessel 1 XG058 13 22mm 2 port valve 1 XG083 7160764 14 Junction wiring box 12...

Страница 27: ...ood House 40 New Road Stourbridge West Midlands DY8 1PA Telephone 01384 442611 Fax 01384 442612 Water Savings Water Related Costs Can Be Reduced By Good Plumbing Practice TAPS MIXERS SHOWERS Unregulated 25 30 l m Regulated 10 12 l m Over 20 l m 5 6 or 8 l m 2 tap half open Fitted with regulator Unregulated 4 Fixing Options For Taps Mixers 1 MK Range Combined Regulators Aerator forscrewingontoTaps ...

Страница 28: ...ing ensure you have a good hold e Taking the lead for team lifts As more than one person is required for these products ensure that one person is taking the lead This may be you so ensure that each person that is helping is made aware oftheweightandoftheitemslistedwithin this assessment Make sure you and any others helping know the route you intend to take that it is clear of any obstructions Neve...

Страница 29: ...TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 5 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 6 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No C...

Страница 30: ...Page 30 NOTES ...

Страница 31: ...Page 31 NOTES ...

Страница 32: ...H Co KG D 35107 Allendorf Telephone 49 6452 70 0 Fax 49 6452 70 2780 www viessmann com Viessmann Limited Hortonwood 30 Telford Shropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com ...

Отзывы: